Sequence of operation of the CERA-1 one-zone system (standard model): 

• 

The CERA-1 unit has a supply and return duct with built-in air valve that regulate the air volume. The Flo-Cross

®

 air fl ow measuring sensor 

®

®

is built into the supply duct to measure the air fl ow.

• 

A central AHU provides fresh air and ensures static pressure in the system. The distribution of air in the home will be determined by 

the manual setting of the air diff users. 

The central AHU unit must function 24/7. 

• 

In normal operation, the measured CO

value (living room) will be used to calculate the required air volume between a minimum air volume 

(MinFlow) at 800 ppm and a maximum required air volume (MaxFlow) at 950 ppm. If the CO

2

 value 

 800 ppm, then the air volume will be equal 

to the MinFlow.

• 

By actuating the pulse switches (kitchen/bathroom) with LED feedback, the air volume in the home can be temporarily set to an increased or 

reduced mode (night/sleep mode).

• 

In increased mode, the required air volume will be maximum regardless of the measured CO2 value; after 60 minutes, the control sequence will 

automatically return to the demand-driven CO

2

 control.

• 

In reduced mode (night-/sleep mode), the required air volume will be set to a fi xed value of 75% MaxFlow, regardless of the CO

2

 reading. After 

13 hours (night/sleep setting), the control sequence will automatically return to normal operation.

• 

In the increased mode, the LED indicator on the transmitter will be on continuously and in the reduced mode it will fl ash slowly.

• 

CERA-1 is also suitable for integration with the bathroom light; the CERA-1 unit will automatically switch to the increased mode after a 5-minute 

delay. After the light in the bathroom is switched off , the increased mode will revert to the previous setting after a 30-minute delay.

• 

Deviations on this control sequence of operation can be discussed; please contact our technical staff . 

• 

CERA-1 PLUS is available for monitoring CO

2

 levels in multiple bedrooms. A CERA-S-TCO2 CO

2

 sensor can be installed in a total of 4 bedrooms 

and the living room. The highest CO

2

 value measured will be used in the calculation of the desired air volume. 

• 

Optionally a humidity sensor can be used in the bathroom/bedroom, which ensures that the CERA unit automatically switches to elevated 

increased mode the moment the humidity rises above a preset percentage. As standard for this type CERA-KLH100-HD-R5V sensor a percentage 

of 70% is used.

TYPE CERA-1

CERA-1 | type NXOJOOB

Control sequence of operation (standard)

CO

2

-sensor

Type: CERA-S-TCO2

Hygrostat

Type: CERA-KLH100-HD-R5V

Summary of Contents for CERA NXOJOOB

Page 1: ...www airselect nl TYPE NXOJOOB TOTAL VENTILATION CONCEPT FOR STACKED HOUSING TOTAL VENTILATION CONCEPT FOR STACKED HOUSING CO2 CONTROLLED FRESH OUTSIDE AIR VENTILATION SYSTEM ONLINE SELECTION TOOL...

Page 2: ...dependent control Low pressure loss Individual room control up to 6 nos rooms High accurate air ow control Flo Cross air ow sensor air ow sensor Plug Play including factory calibrated BACnet controlle...

Page 3: ...s Index TYPE CERA 1 CERA 2 Type designation 4 Technical information 5 Technical information delivery format 6 Speci cation 7 Assembly and installation intructions 8 CERA 1 Dimensions 9 Performance dat...

Page 4: ...t coil O O without reheat coil Position 6 Controls type and function O O without controls Position 7 Sensor B O not applicable B Flo Cross 2 x 12 point averaging 2 x 12 point averaging and signal ampl...

Page 5: ...contain lters or a fan BENG calculation BENG stands for Nearly Zero Energy Buildings and is applicable since 01 01 2021 and did replace the EPC calculation The BENG calculation is required for applyin...

Page 6: ...ogen free The controller is supplied with dedicated CERA 1 or CERA 2 software Upon request the system can be set up and remotely controlled It is recommended to opt for the optional remote setup and m...

Page 7: ...n bearings Completed with Flo Cross 2x12 points 2x12 points averaging and signal amplifying air ow sensors better than 2 5 accuracy even with irregular duct approach Units supplied with DDC controller...

Page 8: ...and measuring tubes must be accessible at all times control equipment is mounted on the inner side and can be reached via a hinged ap The unit must be clean dust free and dry when tted and connected...

Page 9: ...490 C 265 293 333 D 158 158 198 E 350 350 430 F 100 100 120 G 210 210 250 Kg 14 4 14 8 17 0 Model CERA 1 Remarks dimensions 1 All dimensions are in mm 2 Other dimensions available on request Home sid...

Page 10: ...Volume Lw in dB Oct re 1pW Lp values dB A NC NR dB dB dB Lw in dB Oct re 1pW Lp values Lw in dB Oct re 1pW Lp values dB A NC NR TYPE CERA 1 Sound data pressure drop 100 Pa 125 Hz 250 Hz 500 Hz 1000 H...

Page 11: ...cable signal cable Power Outlet 230Vac Power Outlet 230Vac CO sensor push button switch 24V 0V OP1 OP2 OP3 0V 24 V 0 5 V 0 2000 ppm 0 V 0 5 V 0 40 C N A CERA S TCO2 24V 0V OP1 OP2 OP3 0V 24 V 0 5 V 0...

Page 12: ...emand driven CO2 control In reduced mode night sleep mode the required air volume will be set to a xed value of 75 MaxFlow regardless of the CO2 reading After 13 hours night sleep setting the control...

Page 13: ...338 373 453 K x 109 129 L x 118 138 Kg 21 2 23 4 29 2 Model CERA 2 Dimensions en weight CERA 2 CERA 2 type NXOJOOB Dimensions TYPE CERA 2 Remarks dimensions 1 All dimensions are in mm 2 Other dimensi...

Page 14: ...42 31 22 24 59 54 48 42 37 30 34 36 29 24 22 21 22 8 244 517 878 89 72 67 59 54 50 45 33 25 27 61 56 50 45 39 32 22 36 39 33 27 24 22 25 10 305 646 1097 139 X X X X X X X X X X X X X X X X X X X X X X...

Page 15: ...1 OP2 OP3 0V 24 V 0 5 V 0 2000 ppm 0 V 0 5 V 0 40 C N A CERA S TCO2 24V 0V OP1 OP2 OP3 0V 24 V 0 5 V 0 2000 ppm 0 V 0 5 V 0 40 C N A CERA S TCO2 24V 0V OP1 OP2 OP3 0V 24 V 0 5 V 0 2000 ppm 0 V 0 5 V 0...

Page 16: ...volume will be maximum regardless of the measured CO2 value it will be equally 50 50 divided between the two zones After 60 minutes the control sequence will automatically return to the demand driven...

Page 17: ...17 01 2022 Barcol Air B V T 31 0 299 689 300 www barcol air nl www cera systeem nl Changes w o notice or obligation CERA units type NXOJOOB CE Declaration of Conformity TYPE CERA 1 CERA 2...

Page 18: ...BARCOL AIR AIR DISTRIBUTION Cantekoogweg 10 12 1442 LG Purmerend The Netherlands T 31 0 299 689 300 E export barcol air nl OUR TECHNOLOGY YOUR WELLBEING WWW BARCOL AIR NL...

Reviews: