Barcol-Air CERA NXOJOOB Manual Download Page 10

10

© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.

1. Sound data is determined in a reverberation

  room at an independent sound laboratory,

  according to ISO 3741 en ISO 5135 

 standards. 

2. Lw/Oct. (re. 1pW) are sound power levels 

  for discharge and radiated sound. Values 

  < 17 dB  are indicated by “-“. 

3.  The values for insertion loss L

w

do not 

  include end reflection.

4. dB(A), NC and NR index values are sound  

  pressure levels. Sound pressure levels 

  < 20 are indicated by “--“. 

5. The sound pressure levels for discharge 

  sound include the values for an acoustic

  hose in accordance with table 1.  

6.  Lp values are including a room absorption

   of 10 dB/Oct.

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

m/s

l/s

CFM

m³/h

Pa

2

23

50

84

5

63 53 48 44 33 25 21

57 49 43 35 29 18

29 19

4

47

99

168

20

65 57 51 49 40 31 25

63 55 48 42 36 27 22

32 27 22 21

6

70

149

253

42

67 59 53 51 44 35 27

20 67 58 51 46 40 32 26

21 34 32 27 24 19

8

94

198

337

71

68 60 55 53 47 38 28

22 70 61 53 49 43 36 29 22 24 35 35 30 27 22 17 22

10

117

248

421

108

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

2

39

82

139

2

62 49 45 39 30 20

49 45 43 35 27 17

27

4

77

164

279

8

68 57 53 49 40 32 26

22 58 54 50 44 37 29 20

33 27 24 22

6

116

246

418

18

71 62 58 54 46 39 30 24 26 64 59 55 49 43 36 26

36 34 31 27 21 19 23

8

155

328

558

30

74 65 61 58 50 44 33 27 28 68 63 58 53 47 41 29 20 23 38 39 36 31 25 23 27

10

194

410

697

46

76 68 63 61 53 47 36 29 31 71 66 60 56 50 45 32 24 27 40 43 39 34 28 25 30

2

61

129

219

1

54 48 44 39 31 21

52 45 40 34 30 22

21

4

122

258

439

4

61 56 53 49 41 33 23

56 51 45 39 34 27

27 26 22 21

6

183

388

658

9

66 61 58 54 48 40 28

22 59 54 48 42 37 30

30 32 30 27 21 19 22

8

244

517

878

16

69 65 62 58 52 45 32 24 26 61 56 50 45 39 32 22

33 37 35 31 25 22 26

10

305

646

1097

25

71 67 64 62 55 48 35 27 30 62 58 52 46 40 33 23

34 41 39 34 28 25 30

dB

(A

)

NC

NR

125

160

Model

Data referring to inlet

spigot

min.

Δ

Ps

Discharge sound (supply)

Discharge sound (return)

200

Radiated sound

Ve

lo

cit

y

Air Volume

Lw in dB/Oct. (re 1pW)

Lp values

dB

(A

)

NC

NR

dB

dB

dB

Lw in dB/Oct. (re 1pW)

Lp values

Lw in dB/Oct. (re 1pW)

Lp values

dB

(A

)

NC

NR

TYPE CERA-1

Sound data (pressure drop ∆ 100 Pa)

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

m/s

l/s

CFM

m³/h

Pa

2

23

50

84

5

64 56 51 47 38 31 24

57 51 46 40 35 23

30 20

18

4

47

99

168

20

69 61 56 53 45 37 29 22 23 66 58 52 46 41 31 25

35 29 24 24 19

6

70

149

253

42

72 64 58 56 49 41 32 25 27 71 62 55 50 44 36 29 23 25 37 34 29 27 23 19 22

8

94

198

337

71

74 66 60 59 52 44 34 28 29 74 65 57 52 47 40 33 27 29 39 37 33 30 25 22 25

10

117

248

421

108 76 68 61 61 54 46 36 30 31 77 67 59 54 49 42 35 31 32 41 40 36 32 28 23 28

2

39

82

139

2

63 52 48 42 35 26 22

51 47 45 39 34 25

29

4

77

164

279

8

70 60 56 51 44 36 29 22 24 61 56 52 47 42 34 23

34 27 25 23 19

6

116

246

418

18

73 65 60 56 50 43 33 26 28 66 62 57 52 46 40 28

21 37 34 31 28 24 21 24

8

155

328

558

30

76 68 64 60 54 47 36 30 31 70 65 60 55 49 44 32 23 25 39 39 36 32 28 25 28

10

194

410

697

46

78 71 66 63 57 50 38 32 33 73 68 63 57 52 47 34 26 28 40 42 40 35 30 28 31

2

61

129

219

1

57 52 46 41 36 27

52 46 43 38 35 28

23

4

122

258

439

4

64 59 55 51 46 37 26

58 53 49 44 39 33

29 26 23 22 19

6

183

388

658

9

68 64 60 56 51 43 31 23 25 62 57 52 47 42 35 23

32 32 30 27 24 21 23

8

244

517

878

16

72 67 64 60 55 48 35 27 29 65 60 54 49 43 37 26

34 36 35 31 28 24 27

10

305

646

1097

25

74 69 66 63 58 51 37 30 32 67 62 56 50 45 39 28

20 36 40 39 34 31 27 30

Radiated sound

Lw in dB/Oct. (re 1pW)

Lp values

NR

dB

(A

)

NC

NR

125

Model

Data referring to inlet

spigot

min.

Δ

Ps

Discharge sound (supply)

Discharge sound (return)

Ve

lo

cit

y

Air Volume

Lw in dB/Oct. (re 1pW)

Lp values

Lw in dB/Oct. (re 1pW)

Lp values

dB

(A

)

NC

160

200

dB

(A

)

NC

NR

dB

dB

dB

Sound data (pressure drop ∆ 150 Pa)

Additional sound absorption of Sonodec acoustic hose (1 meter)

Hz

125

250

500

1000

2000 4000

dB

17

22

22

27

19

14

7. 

p

s

 is the static pressure loss in the CERA

ss

  unit with the damper fully open.

8. Where an “X” is shown in the table, 

  the unit’s own resistance is > 100 Pa, 

  which means sound levels at 100 Pa 

  are not available.

9. For non standard applications and/or 

  selections please contact our technical staff .

CERA-1 | type NXOJOOB

Performance data

Summary of Contents for CERA NXOJOOB

Page 1: ...www airselect nl TYPE NXOJOOB TOTAL VENTILATION CONCEPT FOR STACKED HOUSING TOTAL VENTILATION CONCEPT FOR STACKED HOUSING CO2 CONTROLLED FRESH OUTSIDE AIR VENTILATION SYSTEM ONLINE SELECTION TOOL...

Page 2: ...dependent control Low pressure loss Individual room control up to 6 nos rooms High accurate air ow control Flo Cross air ow sensor air ow sensor Plug Play including factory calibrated BACnet controlle...

Page 3: ...s Index TYPE CERA 1 CERA 2 Type designation 4 Technical information 5 Technical information delivery format 6 Speci cation 7 Assembly and installation intructions 8 CERA 1 Dimensions 9 Performance dat...

Page 4: ...t coil O O without reheat coil Position 6 Controls type and function O O without controls Position 7 Sensor B O not applicable B Flo Cross 2 x 12 point averaging 2 x 12 point averaging and signal ampl...

Page 5: ...contain lters or a fan BENG calculation BENG stands for Nearly Zero Energy Buildings and is applicable since 01 01 2021 and did replace the EPC calculation The BENG calculation is required for applyin...

Page 6: ...ogen free The controller is supplied with dedicated CERA 1 or CERA 2 software Upon request the system can be set up and remotely controlled It is recommended to opt for the optional remote setup and m...

Page 7: ...n bearings Completed with Flo Cross 2x12 points 2x12 points averaging and signal amplifying air ow sensors better than 2 5 accuracy even with irregular duct approach Units supplied with DDC controller...

Page 8: ...and measuring tubes must be accessible at all times control equipment is mounted on the inner side and can be reached via a hinged ap The unit must be clean dust free and dry when tted and connected...

Page 9: ...490 C 265 293 333 D 158 158 198 E 350 350 430 F 100 100 120 G 210 210 250 Kg 14 4 14 8 17 0 Model CERA 1 Remarks dimensions 1 All dimensions are in mm 2 Other dimensions available on request Home sid...

Page 10: ...Volume Lw in dB Oct re 1pW Lp values dB A NC NR dB dB dB Lw in dB Oct re 1pW Lp values Lw in dB Oct re 1pW Lp values dB A NC NR TYPE CERA 1 Sound data pressure drop 100 Pa 125 Hz 250 Hz 500 Hz 1000 H...

Page 11: ...cable signal cable Power Outlet 230Vac Power Outlet 230Vac CO sensor push button switch 24V 0V OP1 OP2 OP3 0V 24 V 0 5 V 0 2000 ppm 0 V 0 5 V 0 40 C N A CERA S TCO2 24V 0V OP1 OP2 OP3 0V 24 V 0 5 V 0...

Page 12: ...emand driven CO2 control In reduced mode night sleep mode the required air volume will be set to a xed value of 75 MaxFlow regardless of the CO2 reading After 13 hours night sleep setting the control...

Page 13: ...338 373 453 K x 109 129 L x 118 138 Kg 21 2 23 4 29 2 Model CERA 2 Dimensions en weight CERA 2 CERA 2 type NXOJOOB Dimensions TYPE CERA 2 Remarks dimensions 1 All dimensions are in mm 2 Other dimensi...

Page 14: ...42 31 22 24 59 54 48 42 37 30 34 36 29 24 22 21 22 8 244 517 878 89 72 67 59 54 50 45 33 25 27 61 56 50 45 39 32 22 36 39 33 27 24 22 25 10 305 646 1097 139 X X X X X X X X X X X X X X X X X X X X X X...

Page 15: ...1 OP2 OP3 0V 24 V 0 5 V 0 2000 ppm 0 V 0 5 V 0 40 C N A CERA S TCO2 24V 0V OP1 OP2 OP3 0V 24 V 0 5 V 0 2000 ppm 0 V 0 5 V 0 40 C N A CERA S TCO2 24V 0V OP1 OP2 OP3 0V 24 V 0 5 V 0 2000 ppm 0 V 0 5 V 0...

Page 16: ...volume will be maximum regardless of the measured CO2 value it will be equally 50 50 divided between the two zones After 60 minutes the control sequence will automatically return to the demand driven...

Page 17: ...17 01 2022 Barcol Air B V T 31 0 299 689 300 www barcol air nl www cera systeem nl Changes w o notice or obligation CERA units type NXOJOOB CE Declaration of Conformity TYPE CERA 1 CERA 2...

Page 18: ...BARCOL AIR AIR DISTRIBUTION Cantekoogweg 10 12 1442 LG Purmerend The Netherlands T 31 0 299 689 300 E export barcol air nl OUR TECHNOLOGY YOUR WELLBEING WWW BARCOL AIR NL...

Reviews: