1. Safety
1.4
Important warnings for the FLX Power System DPR-2700
Important warnings for the FLX Power System DPR-2700
Products are not liable for any hazards incurred by not following proper safety procedures. Installation, Operation and maintenance
personnel should always follow these safety rules:
1.
Caution - Do not install or remove any FLX Power Recti
fi
er DPR-2700 unit with the AC Breaker On. The AC Breakers must be
switched to the off position prior to inserting a recti
fi
er unit into a shelf.
2.
Before the shelf is operational, the AC input frequency and voltage must be veri
fi
ed, AC break rating and type is adequate, and
other environmental conditions as noted in the speci
fi
cations are met.
3.
The shelf has passed stringent system testing prior to shipment. To avoid electrical shock, the FLX Power System DPR-2700
shelf requires a single ground point permanently connected to earth ground.
4.
An AC Breaker must provide adequate isolation between the shelf input and Commercial AC Main.
5.
The environment should be dust free and controlled by an air condition system. The area must be free of any
fl
ammable vapors
or
fl
uids.
6.
To avoid electrical hazard, the covers must not be removed on any component including the CSU and Recti
fi
ers.
7.
Circuit breakers must be replaced with approved replacement circuit breakers meeting the original design speci
fi
cation.
8.
All AC connections must be made per the latest issue of the National Electrical Code and must also conform to all local codes.
9.
Air
fl
ow: Installation of the power supply in a rack should be such that the amount of air
fl
ow required for safe operation of the
power supply is not compromised. The required space is as follows:
-
Top: 4 inch
-
Bottom: 4 inch
-
Front: 12 inch
-
Rear: 12 inch
10. The power supply should only be installed in a “Restricted Access Location”. The de
fi
nition of a “restricted access location" is
a location for equipment where both of following paragraphs apply:
-
Access can only be gained by SERVICE PERSONS or by USERS who have been instructed about the reasons for the
restriction applied to the location and about the precautions that shall be taken.
-
Access is through the use of the tool or lock and key, or other means of security, and is controlled by the authority responsible
for the location.
11. The equipment is not provided with surge protector. When installing, the external surge protector would be required if AC mains
transient voltage exceeds 2500Vpk.
12. Operating ambient temperature: If installed in a closed or multi rack assembly, the operating ambient temperature of the rack
environment may be higher than the room ambient. Therefore, consideration should be given to install the power supply not in
an environment with an ambient temperature of 33°C or higher.
13. Mechanical loading: Mounting of the power supply in a rack should be such that a hazardous condition is not achieved due to
uneven mechanical loading.
14. Reliable earthing: the power supply should be reliable earthed. Do not connect the ground conductor to the system neutral.
The size of the ground conductor should be minimum 8 AWG.
15. AC input connections: All the AC cables can be connected to shelf main input terminals. The recommended AC wires are:
-
for a Y connection: 8 AWG L1/L2/L3/N
-
for a Delta connection: 6 AWG L1/L2/L3
16. The FLX Power System DPR-2700 is only for connection with the Barco FLX-HUB.
17. A readily accessible disconnect device shall be incorporated in the building installation wiring. The disconnect device shall be
a circuit breaker or a branch fuse according to the following rating: maximum 60A with 3 poles L1 L2 L3.
18. The removable FLX Power Recti
fi
er DPR-2700 units are not HOT SWAPPABLE! The main power must be removed before
unplugging a recti
fi
er.
19. A
fi
re enclosure is required in the end installation. Therefore it is mandatory to mount a full metal plate at the top and bottom of
the FLX Power System DPR-2700. The distances speci
fi
ed in point 9 must be respected.
R59770419 FLX-60 12/05/2010
7
Summary of Contents for FLX-60
Page 1: ...FLX 60 Installation manual R59770419 00 12 05 2010...
Page 6: ...Table of contents 2 R59770419 FLX 60 12 05 2010...
Page 18: ...2 Installation requirements 14 R59770419 FLX 60 12 05 2010...
Page 63: ...4 Installation procedures Image 4 21 R59770419 FLX 60 12 05 2010 59...
Page 64: ...4 Installation procedures 60 R59770419 FLX 60 12 05 2010...
Page 78: ...B Specifications 74 R59770419 FLX 60 12 05 2010...