5.6
Clearances to a non-flammable ceiling
Put a non-flammable insulation plate (false ceiling) of minimum 5 cm thickness at a height
of minimum 50 cm above the appliance.
Alternative without a false ceiling: Make an open space of minimum 50 cm height
between the chimney enclosure top side (complete width and depth of the enclosure) and
the non-flammable ceiling
show the minimum thickness of the insulation plates and the
minimum clearances to a non-flammable ceiling
Make sure the total area of the convection air outlet opening is minimum 300 cm
2
.
1
Chimney enclosure
2
Convection air outlet opening
3
Non-Flammable ceiling
4
Insulation plate (false ceiling)
5
Insulation plates
Figure 10. Clearances to non-flammable ceiling - Front view
Clearances
Unilux-7 75
19