Optional Sensor Performance Verification and Commissioning continued...

2.  Apply Verification Stimulus

A. Apply the stimulus gas during the first minute after the sensor illuminates the ON icon (See Stimulus Preparation and 

Application).  

B. Read and record the VOC output voltage or Main LCD display approximately 2 to 4 minutes following the stimulus 

gas application to determine the dynamic range measurement.  (Dynamic Range Estimate period in figure 19)

C. When the dynamic range estimate period is complete the ON icon will be extinguished.

3.  Termination of Verification Mode 

A. For the last 7 minutes of the start-up period the sensor adapts to its ambient environment.  The VOC sensor will 

maintain its output voltage at 450 ppm CO2 equivalent.  Display units will show 450 ppm equivalents.

B. At 15 minutes the VOC sensor will terminate the start-up period and begin normal operation.
C. The VOC output will now report the VOCs present as CO2 equivalents.

4.  Result Analysis and Recommendations

A. The VOC algorithm requires a dynamic range of greater than 30% for proper operation.  Sensors reporting a 

dynamic range of 30% or less should be considered for replacement. (See Fig 21)

Place 50ml of 70% minimum Isopropyl Alcohol (customer supplied) into a 200ml glass bottle (2oz in an 8oz glass bottle) 

with stopper and allow to reach room temperature (65° to 80°F, 18° to 27°C), a minimum of 15 minutes.
1.   Using a medical grade syringe, remove the stopper from the alcohol bottle, place the tip of the syringe at least half-way 

into the bottle and withdraw a 60 ml sample of the ALCOHOL VAPOR. (NO LIQUID)

2.   Replace the stopper on the alcohol bottle.
3.   Place the end of the syringe -

A.  Over, or into the top ventilation slot of the VOC monitor’s housing for room versions.

B.  Into a knockout opening or directly into the aspiration probe’s top hole for duct mount versions. 

4.  Empty the syringe into the sensor using one continuous motion.

  

Stimulus Preparation and Application

Fig 20: 

Alcohol Bottle 

and Syringe

Fig 21: 

Acceptable Dynamic Range Output

Summary of Contents for VOC

Page 1: ...o AC Power 0 to 5 VDC Output Units 9 to 35 VDC 50 mA Max 9 to 15 VDC recommended 0 to 10 VDC Output Units 15 to 35 VDC 50mA Max 15 VDC recommended Sensing Elements Humidity Capacitive Polymer 2 RH Accuracy VOCs Micro machined Metal Oxide Temp Sensor Thermistor RTD or Semiconductor Mounting 2 x4 J Box or drywall mount screws provided VOC Detection Range 0 to 2 000 CO2 PPM equivalent Response Time L...

Page 2: ...rywall Mounting 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole DO NOT punch the holes or the drywall anchors will not hold Insert a drywall anchor into each hole 4 Drill one 1 2 hole in the middle of t...

Page 3: ...DC Outputs Termination Note Unit is not ready for operation until the 15 minute start up time has elapsed Fig 3 Circuit Board Note For proper operation the jumper on PRG connector of J19 must be connected by only one leg Optional Test and Balance Switch SW1 Sensor Type Low Temp High Temp 1000 RTD 1 02K 41 2 F 1 15K 101 5 F 3000 Thermistor 7 87K 39 8 F 1 50K 106 8 F 10K 2 Thermistor 30 1K 34 9 F 4 ...

Page 4: ...hree arrow icons are used with the ARW option to show VOC levels and their meaning The main display indicates the numeric value of the quantity being displayed The minor display indicates the engineering units of the value such as VOC F C or RH Temperature Setpoint Slide Pot Moving the slide pot enough to change the setpoint by one degree will display the setpoint on the main display if equipped w...

Page 5: ...ay Information Figs 12 and 13 show how to place the unit into field setup mode to adjust the parameter offsets and display functions shown in Table 1 below Take the jumper from the BNK terminals and place it on the PRG terminals The F C jumper is omitted for clarity The major display should read P1 and the minor display should read DSP Use the UP DN buttons See Fig 14 to select the desired page Pr...

Page 6: ...splay Time in Minutes 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zero VOC Sensor Acclimation 5 Dynamic Range Estimate Apply Test Gas Undefined Dynamic Range Calculation Adapting to Environment 22 5 Normal Operation Normal Operation Power ON ON Icon Illuminates ON Icon Extinguished Fig 19 Sensor Start up Timeline BAPI s VOC sensor contains an adaptive self adjusting Volatile Organic Compound VOC sensor ...

Page 7: ... at 450 ppm CO2 equivalent Display units will show 450 ppm equivalents B At 15 minutes the VOC sensor will terminate the start up period and begin normal operation C The VOC output will now report the VOCs present as CO2 equivalents 4 Result Analysis and Recommendations A The VOC algorithm requires a dynamic range of greater than 30 for proper operation Sensors reporting a dynamic range of 30 or l...

Page 8: ...connect sensor and check power wires for proper voltage see specs on pg 1 Wait 15 minutes after a power interruption Check all software parameters Determine if the sensor is exposed to an external environment different from the room conduit draft Check all software parameters If available check the sensor against a calibrated instrument such as a hygrometer Determine if the sensor is exposed to an...

Reviews: