BAPI VOC Installation And Operating Instructions Manual Download Page 4

Installation and Operating Instructions

VOC Room Sensor in the BAPI-Stat 3 Enclosure 

with Differential Ground Configuration

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

29156_ins_voc_room_dif_gnd

4 of 8

rev. 06/05/18

Wire Color

Ground

Black

Tip

White

Ring

Red

Table 1: C35 Wiring

  

Optional Communication Jack Wiring

Fig 5: 

Communication Jack

C35

C35 Communication Jack

(Male jack shown for clarity)

  

User Operation

BAPI Man Icon

Minor Display 0.34” 3-digit Alpha-Numeric

Main Display 0.76” 4-digit Numeric 

Fig 6: 

Optional Display

Optional VOC Level “Arrow” Indicator  

(-ARW Option)

ON Icon for 

Verification and 

Commissioning

The display indicates VOC in PPM, air temperature in degrees Fahrenheit or Celsius, relative humidity in %RH, 

temperature setpoint in degrees Fahrenheit or Celsius and override using the BAPI Man icon.  The three arrow 

icons are used with the –ARW option to show VOC levels and their meaning.
The main display indicates the numeric value of the quantity being displayed.  The minor display indicates the 

engineering units of the value, such as VOC, °F, °C or %RH.

Temperature Setpoint Slide Pot:

 

Moving the slide pot enough to change the setpoint by one degree 

will display the setpoint on the main display if equipped with display. 

The setpoint display will hold for five seconds after moving the slide 

pot.

Override Button:

 

When the override button is pressed on display units, the BAPI Man 

icon will display.  A dry resistance of less than 1 Ohm appears from 

the override output (OVR) to the Ground terminal (GND).  Latching 

the BAPI Man icon to show that the system is in override requires 

that a dry contact on your controller be used to connect terminal 

EXT to ground.

Optional VOC Level Indication via Arrow or 3-Color LED

 (Fig. 7)

VOC level indication is available via a black arrow on the display or 

a three-color LED on the logo plate with green for good, yellow for 

fair and red for poor.

Fig 7: 

VOC Level Indicators

Arrow 

Indicators 

& Legend

LED

Indicator & 

Legend

Note:

 Both 

indicators are 

not available 

together

Summary of Contents for VOC

Page 1: ...o AC Power 0 to 5 VDC Output Units 9 to 35 VDC 50 mA Max 9 to 15 VDC recommended 0 to 10 VDC Output Units 15 to 35 VDC 50mA Max 15 VDC recommended Sensing Elements Humidity Capacitive Polymer 2 RH Accuracy VOCs Micro machined Metal Oxide Temp Sensor Thermistor RTD or Semiconductor Mounting 2 x4 J Box or drywall mount screws provided VOC Detection Range 0 to 2 000 CO2 PPM equivalent Response Time L...

Page 2: ...rywall Mounting 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole DO NOT punch the holes or the drywall anchors will not hold Insert a drywall anchor into each hole 4 Drill one 1 2 hole in the middle of t...

Page 3: ...DC Outputs Termination Note Unit is not ready for operation until the 15 minute start up time has elapsed Fig 3 Circuit Board Note For proper operation the jumper on PRG connector of J19 must be connected by only one leg Optional Test and Balance Switch SW1 Sensor Type Low Temp High Temp 1000 RTD 1 02K 41 2 F 1 15K 101 5 F 3000 Thermistor 7 87K 39 8 F 1 50K 106 8 F 10K 2 Thermistor 30 1K 34 9 F 4 ...

Page 4: ...hree arrow icons are used with the ARW option to show VOC levels and their meaning The main display indicates the numeric value of the quantity being displayed The minor display indicates the engineering units of the value such as VOC F C or RH Temperature Setpoint Slide Pot Moving the slide pot enough to change the setpoint by one degree will display the setpoint on the main display if equipped w...

Page 5: ...ay Information Figs 12 and 13 show how to place the unit into field setup mode to adjust the parameter offsets and display functions shown in Table 1 below Take the jumper from the BNK terminals and place it on the PRG terminals The F C jumper is omitted for clarity The major display should read P1 and the minor display should read DSP Use the UP DN buttons See Fig 14 to select the desired page Pr...

Page 6: ...splay Time in Minutes 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zero VOC Sensor Acclimation 5 Dynamic Range Estimate Apply Test Gas Undefined Dynamic Range Calculation Adapting to Environment 22 5 Normal Operation Normal Operation Power ON ON Icon Illuminates ON Icon Extinguished Fig 19 Sensor Start up Timeline BAPI s VOC sensor contains an adaptive self adjusting Volatile Organic Compound VOC sensor ...

Page 7: ... at 450 ppm CO2 equivalent Display units will show 450 ppm equivalents B At 15 minutes the VOC sensor will terminate the start up period and begin normal operation C The VOC output will now report the VOCs present as CO2 equivalents 4 Result Analysis and Recommendations A The VOC algorithm requires a dynamic range of greater than 30 for proper operation Sensors reporting a dynamic range of 30 or l...

Page 8: ...connect sensor and check power wires for proper voltage see specs on pg 1 Wait 15 minutes after a power interruption Check all software parameters Determine if the sensor is exposed to an external environment different from the room conduit draft Check all software parameters If available check the sensor against a calibrated instrument such as a hygrometer Determine if the sensor is exposed to an...

Reviews: