BAPI Low Range ZPM Installation & Operations Download Page 3

Low Range ZPM - Zone Pressure Sensor

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

3 of 4

 Installation & Operations

38926_ins_ZPM_LR

rev. 04/09/20

LED Off:

 No power is applied or the unit is in 4 to 20 mA Mode

LED On:

 LED is on when power is applied and voltage output is selected. 

When 4 to 20 mA output is selected, the light is on for 2 seconds at power up 

then goes off.

LED Blinking Fast:

 Auto-Zero or Error Mode

LED Blinking Slow:

 The pressure measurement is above or below the 

selected pressure range. Note: When the reading is above or below the 

selected pressure range, the LCD on the face of the unit will alternate between 

showing the actual reading and showing “err”.

Output Termination

Status LED Operation

Fig 7:

 

Status LED on the 

inside of the cover

Auto-Zeroing must be done after the initial setup and after any changing of 

settings.
1. Make sure power is applied

2. Deadhead ports

4. Press the Auto-Zero button for 2 seconds (LED blinks)

5. Remove deadhead after LED stops blinking

6. Attach system tubing

Auto-Zero Operation

Fig 6:

 

Auto-Zero

Button

BAPI recommends wiring the product with power disconnected. 

Proper supply voltage, polarity and wiring connections are important 

to a successful installation.  Not observing these recommendations 

may damage the product and void the warranty.

PWR

Terminal

GND/4-20

Terminal

Vout

Terminal

Fig. 7: 

ZPM Wiring Terminals

To ensure that all wires are properly terminated, twist the stripped ends of each 

wire together before inserting into the terminals. Gently tug on the wire after 

inserting into the terminal to verify a good connection.

Output Signal

PWR Terminal

GND/4-20 Terminal

Vout Terminal

4 to 20 mA

7 to 40 VDC

4 to 20 mA Signal To 

Controller Analog Input Not Used

0 to 5 or 1 to 5 VDC

7 to 40 VDC

or 18 to 32 VAC

To Controller Ground

VDC Signal To Controller 

Analog Input

0 to 10 or 2 to 10 VDC

13 to 40 VDC

or 18 to 32 VAC

To Controller Ground

VDC Signal To Controller 

Analog Input

Table 1: ZPM Termination