24595_ins_BAPI_4_room_humidity
Installation & Operating Instructions
BAPI-Stat 4 Room Humidity Sensor (BA/
B4
-H200 Series)
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
rev. 12/15/17
Specifications subject to change without notice.
Overview
Fig 1:
BAPI-Stat 4
Room Humidity with
Setpoint & Override
The BAPI-Stat 4 Style room unit is available as a humidity only sensor or as
a combination temperature and humidity sensor with optional LCD display,
temperature setpoint adjustment and occupant override. It is available with the
entire line of BAPI temperature sensors.
1 of 5
Mounting
Mounting hardware is provided for both junction box and drywall installation
(junction box installation shown).
JUNCTION BOX
1. Pull the wire through the wall and out of the junction box, leaving about six
inches free.
2. Pull the wire through the hole in the base plate.
3. Secure the plate to the box using the #6-32 x 1/2 inch mounting screws
provided.
4. Terminate the unit according to the guidelines in the
Termination
section.
5. Attach cover by latching it to the top of the base, rotating down and
snapping into place.
6. Secure the cover by backing out the lock-down screws using a 1/16” Allen
wrench until they are flush with the bottom of the cover.
DRYWALL MOUNTING
1. Place the base plate against the wall where you want to mount the sensor.
2. Using a pencil mark out the two mounting holes and the area where the
wires will come through the wall.
3. Drill two 3/16” holes in the center of each marked mounting hole. Insert a drywall anchor into each hole.
4. Drill one 1/2” hole in the middle of the marked wiring area.
5. Pull the wire through the wall and out of the 1/2” hole, leaving about six inches free.
6. Pull the wire through the hole in the base plate.
7. Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
8. Terminate the unit according to the guidelines in the
Termination
section.
9. Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover
by backing out the lock-down screws using a 1/16” Allen wrench until they are flush with the bottom of the cover.
NOTE: In any wall-mount application, the wall temperature and the temperature of the air within thewall cavity can
cause erroneous readings. The mixing of room air and air from within the wall cavity can lead to condensation, erroneous
readings and premature failure of the sensor. To prevent these conditions, seal the conduit leading to the junction box or
fill the box with insulation.
Fig 2:
Mounting to a Junction Box