background image

Configurable temperature Node with thermocouple inputs and a battery integrated into the housing, mounted on a probe

The SureCross

®

 wireless system is a radio frequency network with integrated I/O that

can operate in most environments and eliminate the need for wiring runs. Wireless net-
works are formed around a Gateway, which acts as the wireless network master device,
and one or more Nodes.
This temperature probe is designed for measuring the temperature at three different
depths of a compost pile. A DX80 Node with a battery integrated into the housing trans-
mits the temperature readings to a Gateway.

• Wireless industrial I/O device with three thermocouple inputs
• FlexPower

®

 technology driven by one lithium primary battery integrated into the

housing

• DIP switches for user configuration
• Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multi-

ple Access (TDMA) control architecture ensure reliable data delivery within the unli-
censed Industrial, Scientific, and Medical (ISM) band

• Transceivers provide bidirectional communication between the Gateway and Node,

including fully acknowledged data transmission

• Internal antenna

For additional information, the most recent version of all documentation, and a complete list of accessories, refer to Banner Engineering's
website, 

www.bannerengineering.com/surecross

.

Models

Description

Frequency

I/O

BWA-TPROBE-001

Wireless DX80 Node and temperature
probe

900 MHz ISM Band

Inputs: Three thermocouple

BWA-TPROBE-002

2.4 GHz ISM Band

DX80N9C-16999

DX80 Node (no probe assembly)

900 MHz ISM Band

DX80N2C-16997

2.4 GHz ISM Band

These Nodes are powered by an internal battery. All batteries must be ordered separately.

WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious
injury or death.
 This device does NOT include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-
energized sensor output condition.

The SureCross

®

 DX80 Wireless Network

The SureCross

®

 DX80 wireless I/O network provides reliable monitoring without the burden of wiring or conduit installation. The Sure-

Cross wireless network can operate independently or in conjunction with a host system, PLC, and/or PC software.
Each wireless network system consists of one Gateway and one or more Nodes. Devices ship with factory defined inputs and outputs
that may be all discrete, all analog, or a mix of discrete and analog I/O.

SureCross Temperature Probe with DX80 Node

 

 

P/N 156525 rev. -

3/15/2013

0 156525

6

Summary of Contents for SureCross Series

Page 1: ...ation and a complete list of accessories refer to Banner Engineering s website www bannerengineering com surecross Models Description Frequency I O BWA TPROBE 001 Wireless DX80 Node and temperature pr...

Page 2: ...rolling other devices or performing calculations Host connected systems can contain up to 15 Nodes when using Rotary Dial Addressing Mode or 47 Nodes when using Extended Addressing Mode within a singl...

Page 3: ...ing without damaging the ribbon cable or the pins the cable plugs into 3 Gently unplug the ribbon cable from the board mounted into the bottom housing For integrated battery models no ribbon cable and...

Page 4: ...DIP switch to the ON position Thermocouple Type Use DIP switches 5 6 7 and 8 to select the thermocouple type The default position is the OFF position for all switches setting the thermocouple to a J t...

Page 5: ...es are communicating properly A Node will not sample its inputs until it is communicating with the Gateway to which it is bound When testing communication between the Gateway and Node all radios and a...

Page 6: ...re is a risk of explosion if the battery is replaced incorrectly 4 After replacing the battery allow up to 60 seconds for the device to power up When removing the battery press the battery towards the...

Page 7: ...eport Rate 16 seconds Accuracy 0 1 of full scale reading 0 8 C Resolution 0 1 C 24 bit A D converter Thermistor used for CJC Model BWA THERMISTOR 001 Accuracy 0 4 C 10 to 50 C Up to 0 8 C 40 to 85 C R...

Page 8: ...ent Banner Engineering Corp will repair or replace free of charge any product of its manufacture which at the time it is returned to the factory is found to have been defective during the warranty per...