Switches
Device Settings
1
2
3
4
5
6
7
8
Thermocouple, E-Type
OFF
ON
OFF
OFF
Thermocouple, G-Type
OFF
ON
OFF
ON
Thermocouple, K-Type
OFF
ON
ON
OFF
Thermocouple, L-Type
OFF
ON
ON
ON
Thermocouple, M-Type
ON
OFF
OFF
OFF
Thermocouple, N-Type
ON
OFF
OFF
ON
Thermocouple, P-Type
ON
OFF
ON
OFF
Thermocouple, R-Type
ON
OFF
ON
ON
Thermocouple, S-Type
ON
ON
OFF
OFF
Thermocouple, T-Type
ON
ON
OFF
ON
Thermocouple, U-Type
ON
ON
ON
OFF
Modbus or UCT configured (overrides DIP switches)
ON
ON
ON
ON
* Default configuration
** In high resolution mode, the temperature = (Modbus register value) ÷ 20. In low resolution mode, the temperature = (Modbus register
value) ÷ 2.
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In
rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network
is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and receive informa-
tion from the Gateway to which they are bound. In extended address mode, wireless networks may contain up to 48 radio devices. For
more information on extended address mode, refer to the SureCross
™
Wireless I/O Network product manual.
The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address mode, change
the DIP switch to the ON position.
Discrete Input Type
Select the type of discrete input sensors to use with this device: sourcing (PNP) sensors or sinking (NPN) sensors.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.
Temperature Resolution
When set to high resolution, temperature values are stored to the nearest tenth (0.1) of a degree (default position). To measure tempera-
tures above 1600 degrees Fahrenheit or 1600 degrees Celsius, switch the DIP switch to the ON position and use low resolution mode. In
high resolution, the device cannot store values larger than 1600.
Temperature Units
Use the DIP switch to specify if the temperature is stored in degrees Fahrenheit or Celsius. The default position is OFF, setting the
temperature to Fahrenheit. For Celsius measurements, set this switch to the ON position.
Thermocouple Type
Use DIP switches 5, 6, 7, and 8 to select the thermocouple type. The default position is the OFF position for all switches, setting the
thermocouple to a J-type thermocouple.
Supported Thermocouple Types
The thermocouple Node is configured, by default, to use J-type thermocouples. The following thermocouples are available by configuring
the Node.