background image

Switch configurable temperature Node with thermocouple/thermistor inputs and two discrete inputs (powered by external battery module

only)

For additional information, updated
documentation, and accessories, re-
fer to Banner Engineering's website, 

www.bannerengineering.com/sure-
cross

.

The SureCross

®

 wireless system is a radio frequency network with integrated I/O that can oper-

ate in most environments and eliminate the need for wiring runs. DX99 wireless networks are
formed around a Gateway, which acts as the wireless network master device, and one or more
Intrinsically Safe Nodes.

• Wireless industrial I/O device with two selectable discrete inputs and up to three configurable

thermocouple inputs (defaults to J-type)

• FlexPower

®

 power input requires power from the DX81H Battery Supply Module

• One thermistor input used for integrated cold junction compensation (CJC)
• DIP switches for user configuration
• Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple Access

(TDMA) control architecture ensure reliable data delivery within the unlicensed Industrial,
Scientific, and Medical (ISM) band

• Transceivers provide bidirectional communication between the Gateway and Node, including

fully acknowledged data transmission

• Lost RF links are detected and relevant outputs set to user-defined conditions
• DX99 Polycarbonate housings are certified for use in Class I, Division 1, Groups A, B, C, D;

and Zone 0 (Category 1G) when properly installed in accordance with the National Electrical
Code, the Canadian Electrical Code, or applicable local codes/regulations

Model

Frequency

I/O

DX99N9X2S2N0T4X0A0

900 MHz ISM Band

Inputs: Two selectable discrete, three thermocouple, one thermistor
(for CJC)

DX99N2X2S2N0T4X0A0

2.4 GHz ISM Band

Internal antenna models are also available. For more information, contact your local Banner Engineering Corp. representative.

WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious
injury or death.
 This device does not include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-
energized sensor output condition.

SureCross User Configuration Tool

The User Configuration Tool (UCT) offers an easy way to link I/O points in your wire-
less network, view I/O register values graphically, and set system communication pa-
rameters when a host system is not part of the wireless network.
The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1 Watt
radios, BWA-HW-006 can be used for all other radios) converter cable to pass infor-
mation between your computer and the Gateway. Download the most recent revi-
sions of the UCT software from Banner Engineering's website: 

http://www.banneren-

gineering.com/wireless

.

Setting Up Your Wireless Network

To set up and install your wireless network, follow these steps.

Disconnect the power from your SureCross devices.

1. Configure the DIP switches of all devices.
2. Connect the sensors to the SureCross devices.

SureCross DX99 FlexPower Thermocouple Node

(Polycarbonate Housing)

 

 

P/N 142498 Rev. E

6/21/2013

0 142498

0

Summary of Contents for SureCross FlexPower DX99 Series

Page 1: ...de the Canadian Electrical Code or applicable local codes regulations Model Frequency I O DX99N9X2S2N0T4X0A0 900 MHz ISM Band Inputs Two selectable discrete three thermocouple one thermistor for CJC DX99N2X2S2N0T4X0A0 2 4 GHz ISM Band Internal antenna models are also available For more information contact your local Banner Engineering Corp representative WARNING Not To Be Used for Personnel Protec...

Page 2: ...ot be recognized if power isn t cycled to the device Accessing the Internal DIP Switches To access the internal DIP switches follow these steps 1 Unscrew the four screws that mount the cover to the bottom housing 2 Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into 3 Gently unplug the ribbon cable from the board mounted into the bottom housing 4 Re...

Page 3: ...on To use extended address mode change the DIP switch to the ON position Discrete Input Type Select the type of discrete input sensors to use with this device sourcing PNP sensors or sinking NPN sensors Modbus User Configuration Tool UCT or DIP Switch Configured In Modbus UCT Configured mode the device parameters are changed using the User Configuration Tool UCT or a Modbus command All DIP switch ...

Page 4: ...I1 GND Ax and Ax Analog IN x Analog inputs for devi ces requiring more than one connection such as thermocouples or RTDs When there is no Ax use Ax as an analog input DIx Discrete IN x GND Ground dc common connection 1 2 3 4 5 FlexPower 3 blue dc common GND 5 gray 3 6V dc Only use the DX81H Bat tery Supply Module to power this device LED Behavior for the Nodes After powering up and binding the Gat...

Page 5: ...exPower or integra ted battery SureCross radio into storage mode press and hold button 1 for five seconds The radio is in storage mode when the LEDs stop blinking but in some models the LCD remains on for an additional minute after the radio enters storage mode After a device has entered storage mode you must wait one minute before waking it During normal operation the SureCross radio devices ente...

Page 6: ...95 max relative non condensing Radiated Immunity 10 V m 80 2700 MHz EN61000 6 2 Shock and Vibration IEC 68 2 6 and IEC 68 2 7 Shock 30g 11 millisecond half sine wave 18 shocks Vibration 0 5 mm p p 10 to 60 Hz Refer to the SureCross DX80 Wireless I O Network Product Manual p n 132607 for installation and waterproofing instructions Operating the devi ces at the maximum operating conditions for exten...

Page 7: ...ries using the antenna that ships with the product When using other antennas verify you are not exceeding the transmit power levels allowed by local governing agencies Consult with Banner Engineering Corp if the destination country is not on this list Violating Warnings The manufacturer does not take responsibility for the violation of any warning listed in this document Make no modifications to t...

Page 8: ... STRICT LIABILITY NEGLIGENCE OR OTHERWISE Banner Engineering Corp reserves the right to change modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp SureCross DX99 FlexPower Thermocouple Node Polycarbonate Housing www bannerengineering com tel 763 544 3164 ...

Reviews:

Related manuals for SureCross FlexPower DX99 Series