04200s Device Name
Address (4xxxx)
Name
Format
4201–4209
Name characters 1-18
ASCII
04300s Software Information
Address (4xxxx)
Name
Format
4301–4303
RF firmware p/n
ASCII, read only
4304–4305
RF firmware version
ASCII, read only
4306–4308
RF EEPROM part number, digits 1–6
ASCII, read only
4309–4310
RF EEPROM version number, characters
1–3
ASCII, read only
4311–4313
LCD firmware p/n
ASCII, read only
4314–4315
LCD firmware version
ASCII, read only
4316–4318
LCD EEPROM part number, digits 1–6
ASCII, read only
4319–4320
LCD EEPROM version number, characters
1–3
ASCII, read only
06400s Message Parameters
Strings stored in ASCII format are read as two characters per Modbus register. The lower numbered Modbus register contains the right-
most characters in the string. Within a given Modbus register, the upper byte contains the ASCII character that goes to the right of the
character in the lower byte.
Address (4xxxx)
Name
Format
6401
Device address
Hex
6402
Parent address
Hex, read only
Storing a Model Number
For example, the model number 148691 is stored as shown below.
Address (4xxxx)
Name
Modbus Register Value (in
hex)
Character Representation
4111
Model number digits 6-5
0x3139
1 9
4112
Model number digits 4-3
0x3638
6 8
4113
Model number digits 2-1
0x3431
4 1
Parameters Stored as Numbers
Parameters stored as number values (not ASCII) read out directly as 16-bit values. Examples of parameters of this type include the
Parent Address or Device Address.
Address (4xxxx)
Name
Value (in hex)
Value (decimal)
6401
Device address
0x002A
42
6402
Parent address
0x0023
35
SureCross MultiHop Data Radio
6
www.bannerengineering.com - tel: 763-544-3164
P/N 148345 Rev. B