R70SR SNAP SIGNAL™ Serial Data Radio
June 23, 2023
page
9
•
•
DX80 Performance Wireless I/O Network Instruction Manual:
MultiHop Data Radio Instruction Manual:
Specifications for the R70xR Models
Radio Range
900 MHz, 500 mW: Up to 1.6 km (1 mile) (internal antenna)
2.4 GHz, 65 mW: Up to 1000 m (3280 ft) with line of sight (in
ternal antenna)
Antenna Minimum Separation Distance
900 MHz, 500 mW: 4.57 m (15 ft)
2.4 GHz, 65 mW: 0.3 m (1 ft)
Radio Transmit Power
900 MHz, 500 mW: 27 dBm
2.4 GHz, 65 mW: 18 dBm (65 mW) conducted, less than or
equal to 20 dBm (100 mW) EIRP
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Communication Protocols
Modbus® RTU, Modbus/TCP, EtherNet/IP™
EtherNet/IP™ is a trademark of ODVA, Inc.
Modbus®
is a reg
istered trademark of Schneider Electric USA, Inc.
Security Protocols
TLS, SSL, HTTPS
900 MHz Compliance
Radio module is indicated by the product label marking
Contains FCC ID: UE3RM7023: FCC Part 15, Subpart C,
15.247
Contains IC: 7044ARM7023
2.4 GHz Compliance (SX243 Radio Module)
Radio module is indicated by the product label marking
Contains FCC ID: UE3SX243: FCC Part 15, Subpart C,
15.247
Radio Equipment Directive (RED) 2014/53/EU
ETSI/EN: EN 300 328 V2.2.2 (2019-07) [RED HarmStds]
Contains IC: 7044A-SX243
ANATEL: 037372204042
Radio Data Transfer Rate
900 MHz: 300 kbps
2.4 GHz: 250 kbps
Supply Voltage
10 V DC to 30 V DC
(
Outside the USA: 12 V DC to 24 V DC,
± 10%
)
For European applications, power this device from a Limited
Power Source as defined in EN 609501.
Average Current for 900 MHz Radios (1500 byte packets at 50 ms
intervals)
Client Mode: 0.12 A at 12 V; 0.06 A at 24 V
Server Mode: 0.03 A at 12 V; 0.017 A at 24 V
Average Current for 2.4 GHz Radios (1500 byte packets at 50 ms
intervals
Client Mode: 0.035 A at 12 V; 0.02 A at 24 V
Server Mode: 0.022 A at 12 V; 0.014 A at 24 V
Interface
Two bi-color LED indicators
One button
(under the small round cover)
Construction
Base: Black polycarbonate
Cover: Translucent gray polycarbonate
Operating Conditions
–40 °C to +85 °C (–40 °F to +185 °F)
95% maximum relative humidity (non-condensing)
Radiated Immunity:
10 V/m (EN 61000-4-3)
Operating the devices at the maximum operating conditions
for extended periods can shorten the life of the device.
Environmental Ratings
IP65
For installation and waterproofing instructions, go
to
and search for the complete
instruction manual
Shock and Vibration
All models meet IEC 60068-2-6 and IEC 60068-2-27 testing
criteria
Shock: 30G 11 ms duration, half sine wave per IEC
60068-2-27
Vibration: 10 Hz to 55 Hz, 0.5 mm peak-to-peak amplitude per
IEC 60068-2-6
Certifications
Banner Engineering BV
Park Lane, Culliganlaan 2F bus 3
1831 Diegem, BELGIUM
(CE/UKCA approval only applies to 2.4 GHz models)
Dimensions for the R70SR
All measurements are listed in millimeters, unless noted otherwise.
© Banner Engineering Corp.