![Banner Sure Cross DXM700-B Series Instruction Manual Download Page 54](http://html1.mh-extra.com/html/banner/sure-cross-dxm700-b-series/sure-cross-dxm700-b-series_instruction-manual_471859054.webp)
Figure 31. Mail server settings
At the bottom of the screen, define the recipient to receive emails. These recipients for email can be selected in the
threshold definition for sending alert messages.
8.5.6 Define Threshold Rules for Email
To define a threshold, go to Action Rules > Thresholds. Depending upon which recipients are defined, select the
appropriate email checkbox for the threshold rule (under Email/SMS on state transition). When the threshold rules goes
active or inactive, an email is generated.
Figure 32. Creating a threshold rule
8.5.7 Define Log File Parameters for Emailing Log Files
The DXM700 can email log files generated on the device.
Before emailing log files, set the Mail and Messaging parameters to provide the login credentials. When using Ethernet,
verify the IP address settings are defined on the Network screen. Set the DXM700 time, under Settings > General, so that all
data is properly time stamped.
Select the registers to log on the Local Registers > Register Configuration screen. Define the setup of the log file using the
Settings > Logging screen. Typical settings are shown.
1. Enable the log and timestamp with every entry.
2. Enter the filename, log rate, and the maximum file size to send via email (5 to 10k is an efficient size for a cellular
connection).
3. Define the email address.
Sure Cross
®
DXM700-Bx Wireless Controller
54
www.bannerengineering.com - Tel: + 1 888 373 6767