Banner SI-HG63 Series Instruction Manual Download Page 7

8. Install a new red plastic washer (from the accessories bag included with the switch) onto the switch cylinder.

Figure 18. Install a new plastic washer

9. If the hinge position on the switch is being changed (changing from a left hinge to a right, for example), remove the

rectangular plug from the switch housing and attach the hinge to that side. Install the hinge onto the switch and rotate 30° to

seat. Fasten the switch to the hinge using the supplied tool and the screws removed in step 1. The countersunk screw max.

torque is 2 Nm.

Figure 19. Change the hinge position

10. Set the new switch point setting as required.

Electrical Installation

WARNING:

Risk of electric shock

Use extreme caution to avoid electrical shock. Serious injury or death could result.

Always disconnect power from the safety system (for example, device, module, interfacing, etc.),
guarded machine, and/or the machine being controlled before making any connections or replacing any
component. Lockout/tagout procedures might be required. Refer to OSHA 29CFR1910.147, ANSI
Z244-1, or the applicable standard for controlling hazardous energy.

Make no more connections to the device or system than are described in this manual. Electrical
installation and wiring must be made by a Qualified Person

1

 and must comply with the applicable

electrical standards and wiring codes, such as the NEC (National Electrical Code), NFPA 79, or IEC
60204-1, and all applicable local standards and codes.

Connection to a Machine

Electrical connection is via a 6-pin dual-key M12/micro-style QD and cordsets (see 

Cordsets 

on page 12) or via the integral cable

of the IP69 models.
Perform a risk assessment to determine the appropriate level of safety circuit performance (integrity) and the means of interfacing

the switch(es) with the machine control circuit. While Banner Engineering always recommends the highest level of safety in any

application, the user is responsible to safely install, operate, and maintain each safety system and comply with all relevant laws and

regulations.
To ensure the highest level of reliability (Control Reliable or Category 4, for example), wire the positively-driven safety contacts

(safety contacts that are closed when the actuator is engaged) 

from each of two individual safety switches per interlock guard

in a dual channel hookup to a safety module (for example, ES-FA-9AA), safety controller (for example, SC/XS26-2), or the safety

related part of the machine control that complies with the required level of safety performance.

1

A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has
successfully demonstrated the ability to solve problems relating to the subject matter and work.

SI-HG(Z)63 Hinge Wing Safety Interlock Switch

 

 

P/N 129465 Rev. G

www.bannerengineering.com - Tel: + 1 888 373 6767

7

Summary of Contents for SI-HG63 Series

Page 1: ...nless Steel Inline QD With QD facing down switch is mounted on left side of hinge SI HGZ63FQDL Zinc Die cast SI HG63F5ML W Stainless Steel Inline Cable With cable exiting down switch is mounted on lef...

Page 2: ...ver panel barrier or other physical means that separates an individual from a hazard The SI HG Z 63 will issue a signal to the machine control system to prevent or stop halt hazardous situations when...

Page 3: ...se requirements Pass through hazards and Perimeter Guarding A pass through hazard is associated with applications where personnel may pass through a safeguard which issues a stop command to remove the...

Page 4: ...nd that the guard or gate swings freely throughout its range of motion without binding If binding is noticed repeat the Mechanical Installation on page 3 2 Place the guard in its closed and latched po...

Page 5: ...in a new location for example Changing the setting requires replacement of the red plastic washer See Replacement Accessory Kit on page 13 for a kit that includes a replacement washer The hinge must...

Page 6: ...nto the enclosure until the switch cylinder arrow aligns with mark B on the switch housing The switch element should sink into the enclosure during this process Figure 16 Align to B 7 Press the switch...

Page 7: ...codes such as the NEC National Electrical Code NFPA 79 or IEC 60204 1 and all applicable local standards and codes Connection to a Machine Electrical connection is via a 6 pin dual key M12 micro styl...

Page 8: ...reliability OSHA 29CFR1910 or ANSI B11 19 or Category 3 or 4 ISO 13849 1 This is required to provide monitoring for safety switch failure and to provide the necessary reset routine as required by NFP...

Page 9: ...r minute Switching Angle NC Contact 3 Positive opening 6 wear can cause increase by 2 NO Contact 9 Tolerance for all angles 1 5 Mechanical Load SI HG63 FR1 1800 N max FR2 750 N max FA 1800 N max SI HG...

Page 10: ...mm 1 30 18 mm 0 71 4 0 mm 0 16 19 5 mm 0 77 Figure 23 Model SI HG Z 63F5MB 8 5 mm 0 33 191 0 mm 7 52 10 5 mm 0 41 37 0 mm 1 46 37 0 mm 1 46 19 5 mm 0 77 50 5 mm 1 99 63 0 mm 2 48 50 5 mm 1 99 82 0 mm...

Page 11: ...ning direction assuming that the point has not been finely adjusted In the table find the B row of 900 and then follow over to the 6 column and note the number 94 1 mm The approximate opening in the g...

Page 12: ...utputs with Ethernet SC26 2de XS26 2de 26 convertible I O and 2 redundant solid state safety outputs with display and Ethernet SC10 2roe 10 inputs 2 redundant relay safety outputs 3 contacts each ISD...

Page 13: ...erity of the operating environment and the frequency of switch actuations Adjust repair or replace components as needed If inspection reveals contamination on the switch thoroughly clean the switch an...

Page 14: ...lenheim Court Wickford Essex SS11 8YT Great Britain Banner Engineering Corp Limited Warranty Banner Engineering Corp warrants its products to be free from defects in material and workmanship for one y...

Reviews: