Banner SI-HG63 Series Instruction Manual Download Page 11

Figure 25. Model SI-HG(Z)63F5MRR

4.0 mm

(0.16")

127.5 mm

(5.02")

63.0 mm

(2.48")

12.0 mm

(0.47")

82.0 mm

(3.23")

50.5 mm

(1.99")

37.0 mm

(1.46")

 51.0 mm

(2.01")

45.0 mm

(1.77")

4.0 mm

(0.16")

Guard Opening Calculation (before switching)

The size opening between the machine frame and the guard can be estimated based on the table provided. This can assist in

determining safety distance as described by ANSI B11.19 or ISO 13857.

Example

A guard with a 40 mm aluminum profile (A) and a width of 900 mm (B) is safeguarded by SI-HG(Z)63 safety interlocking switch. The

switching point is set (fixed) while guard is closed, the positive-opening switching point is set at α = 6° in the opening direction

(assuming that the point has not been finely-adjusted).
In the table, find the "B" row of "900" and then follow over to the 6° column and note the number (94.1 mm). The approximate

opening in the guard at the switching point (C1) can be found by subtracting the width of the guard.

C1 = C – A = 94.1 mm – 40 mm = 54.1 mm

 (at initial installation).

where:

α = Opening angle of the guard at the point of switching

A

 = Width of the guard in mm

B

 = Length of the guard in mm

C

 = Distance travel by outside of guard

C1

 = Size of the opening in the guard at the point of switching

α

6° 

B mm

C mm

100

5.2

7.0

8.7

10.5

12.2

13.9

15.6

200

10.5

14.0

17.4

20.9

24.4

27.8

31.3

300

15.7

20.9

26.1

31.4

36.6

41.8

46.9

400

20.9

27.9

34.9

41.8

48.7

55.7

62.6

SI-HG(Z)63 Hinge Wing Safety Interlock Switch

 

 

P/N 129465 Rev. G

www.bannerengineering.com - Tel: + 1 888 373 6767

11

Summary of Contents for SI-HG63 Series

Page 1: ...nless Steel Inline QD With QD facing down switch is mounted on left side of hinge SI HGZ63FQDL Zinc Die cast SI HG63F5ML W Stainless Steel Inline Cable With cable exiting down switch is mounted on lef...

Page 2: ...ver panel barrier or other physical means that separates an individual from a hazard The SI HG Z 63 will issue a signal to the machine control system to prevent or stop halt hazardous situations when...

Page 3: ...se requirements Pass through hazards and Perimeter Guarding A pass through hazard is associated with applications where personnel may pass through a safeguard which issues a stop command to remove the...

Page 4: ...nd that the guard or gate swings freely throughout its range of motion without binding If binding is noticed repeat the Mechanical Installation on page 3 2 Place the guard in its closed and latched po...

Page 5: ...in a new location for example Changing the setting requires replacement of the red plastic washer See Replacement Accessory Kit on page 13 for a kit that includes a replacement washer The hinge must...

Page 6: ...nto the enclosure until the switch cylinder arrow aligns with mark B on the switch housing The switch element should sink into the enclosure during this process Figure 16 Align to B 7 Press the switch...

Page 7: ...codes such as the NEC National Electrical Code NFPA 79 or IEC 60204 1 and all applicable local standards and codes Connection to a Machine Electrical connection is via a 6 pin dual key M12 micro styl...

Page 8: ...reliability OSHA 29CFR1910 or ANSI B11 19 or Category 3 or 4 ISO 13849 1 This is required to provide monitoring for safety switch failure and to provide the necessary reset routine as required by NFP...

Page 9: ...r minute Switching Angle NC Contact 3 Positive opening 6 wear can cause increase by 2 NO Contact 9 Tolerance for all angles 1 5 Mechanical Load SI HG63 FR1 1800 N max FR2 750 N max FA 1800 N max SI HG...

Page 10: ...mm 1 30 18 mm 0 71 4 0 mm 0 16 19 5 mm 0 77 Figure 23 Model SI HG Z 63F5MB 8 5 mm 0 33 191 0 mm 7 52 10 5 mm 0 41 37 0 mm 1 46 37 0 mm 1 46 19 5 mm 0 77 50 5 mm 1 99 63 0 mm 2 48 50 5 mm 1 99 82 0 mm...

Page 11: ...ning direction assuming that the point has not been finely adjusted In the table find the B row of 900 and then follow over to the 6 column and note the number 94 1 mm The approximate opening in the g...

Page 12: ...utputs with Ethernet SC26 2de XS26 2de 26 convertible I O and 2 redundant solid state safety outputs with display and Ethernet SC10 2roe 10 inputs 2 redundant relay safety outputs 3 contacts each ISD...

Page 13: ...erity of the operating environment and the frequency of switch actuations Adjust repair or replace components as needed If inspection reveals contamination on the switch thoroughly clean the switch an...

Page 14: ...lenheim Court Wickford Essex SS11 8YT Great Britain Banner Engineering Corp Limited Warranty Banner Engineering Corp warrants its products to be free from defects in material and workmanship for one y...

Reviews: