Sensor Programming

1.  Mount the sensor securely. Align the sensor with the background target, making the 

face of the Sensor as parallel as possible to the background target.

   In programming mode (only after the TEACH push button is pressed), the red Signal 

LED will flash faster as the alignment improves; solid ON is best. If the red Signal LED 

does not flash, then the background target is not sufficient and a different target must 

be used, such as a metal plate or a corner cube reflector.

2.  Verify that the area between the sensor and the background is clear, and follow the 

programming procedure in the table below.

General Notes on Programming

•   Once the sensor enters TEACH mode, it will default to the previous settings and exit 

TEACH mode after one minute.

•   To exit TEACH mode and return to the previous settings, push and hold the TEACH 

push button (or pulse the remote line) for more than two seconds.

4

Procedure

Result

Push Button

Remote Line 

0.0 sec. < T < 0.8 sec.

 

Programming 

Mode

•  Push and hold TEACH 

push button until 
Output LEDs turn 
ON Red

•  No action required; sensor is ready to be 

aligned and programmed

Power LED: 

OFF 

Output LEDs: 

ON Red 

Signal LED:

  Flashes faster as background 

signal strength increases (i.e., 
as alignment improves); solid 
ON is best

TEACH 

Background 

Reference 

Target

•  Press and release TEACH 

push button

• Pulse the remote line

Teach Accepted

Power LED: 

ON 

Output LEDs:

 OFF 

Signal LED:

 ON solid

Teach Unacceptable

Power LED: 

OFF 

Output LEDs: 

ON 

Sensor defaults to program mode.

Summary of Contents for R-GAGE QT50R Series

Page 1: ...requency modulated continuous wave FMCW radar technology Detects objects up to 7 2 m 24 away using a fixed background reference target up to 8 m 26 away Detection is unaffected by wind or changing air temperatures Easy to set up using sealed push button or remote wire Operates in Industrial Scientific and Medical ISM telecommunication band no special license required 15 to 30V dc operation Rugged ...

Page 2: ... determine the distance from the sensor to the vehicle based on the time delay of the return signal The sensor is configured to operate like a retroreflective photoelectric sensor See Figure 3 Figure 3 Threshold automatically placed at 90 of distance to background target that is taught NOTE The MODE button on this model is not functional Background Range 4 to 8 m 13 to 26 Dead Zone 0 5 m 1 6 Backg...

Page 3: ...gramming procedure in the table below General Notes on Programming Once the sensor enters TEACH mode it will default to the previous settings and exit TEACH mode after one minute To exit TEACH mode and return to the previous settings push and hold the TEACH push button or pulse the remote line for more than two seconds 4 Procedure Result Push Button Remote Line 0 02 sec T 0 8 sec Programming Mode ...

Page 4: ...sensor so the center of the beam strikes the corner of the tunnel beyond the far rail as shown in Figure 4 2 Make sure the area between the sensor and the background is clear and press the TEACH button until the Output LEDs turn ON red 3 Align the sensor The red Signal LED will flash faster as alignment improves solid ON is best 4 Press the TEACH button again The Output LEDs turn OFF and the red S...

Page 5: ... programming button for setting background reference Operating Temperature 20 to 55 C 4 to 131 F Environmental Rating IEC IP67 NEMA 6 Connections 2 m 6 5 or 9 m 30 5 conductor shielded PVC jacketed attached cable or integral 5 pin Euro style QD Certifications and ETSI EN 300 440 or FCC Part 15 depending on model Status Indicators Power LED Indicates OFF Power is OFF ON Green Power is ON Signal LED...

Page 6: ...d that the shield wire be connected to earth ground or dc common Shielded cordsets are recommended for all QD models bk gy bn bu wh 15 30V dc shield 0 2V dc Load 1 Load 2 Dimensions 38 1 mm 1 50 46 1 mm 1 82 R45 0 mm R1 77 66 0 mm 2 60 84 2 mm 3 31 33 0 mm 1 30 37 0 mm 1 46 74 1 mm 2 92 50 8 mm 2 00 50 8 mm 2 00 19 7 mm 0 78 37 0 mm 1 46 M30 X 1 5 ISO 6g 4X Ø4 4 mm Ø 0 17 34 2 mm 1 35 Cabled Model...

Page 7: ...it clamp with swivel black reinforced thermoplastic polyester Stainless steel hardware included SMB30MM 30 mm 11 gauge stainless steel bracket with curved mounting slots for versatile orientation Clearance for M6 1 4 hardware 50 8 mm 2 00 58 7 mm 2 31 66 5 mm 2 62 30 0 mm 1 18 30 x 1 5 mm internal thread 29 0 mm 1 14 12 7 mm 0 50 35 1 mm 1 38 35 1 mm 1 38 69 9 mm 2 75 7 1 mm 0 28 x 90 2 Slots R 25...

Page 8: ...g Corp warrants its products to be free from defects for one year Banner Engineering Corp will repair or replace free of charge any product of its manufacture found to be defective at the time it is returned to the factory during the warranty period This warranty does not cover damage or liability for the improper application of Banner products This warranty is in lieu of any other warranty either...

Reviews: