Action
Result
Pulse the remote input 1 to 6 times to select the desired mode.
Pulses
Mode
1
T
Alarm
2
T
T
T
Health
3
T
T
T
T
T
Swtch
4
T
T
T
T
T
T
T
Swtch
5
T
T
T
T
T
T
T
T
T
Wnd
6
T
T
T
T
T
T
T
T
T
T
T
Wnd
The selected mode flashes and the sensor
returns to Run mode.
3.5.8 Switch Point Reference (SPtRef)
The SPtRef menu only displays for a discrete output when it is set to switch mode. The SPtRef settings, object or
background, for the two discrete outputs are set independently. This setting cannot be changed with remote teach.
•
Object (default). Object mode sets the switching threshold just past the location of the taught object, farther away
from the sensor's face.
•
Background. Background mode sets the switching threshold in front of the taught object, closer to the sensor's
face.
The distance between the surface of the taught object and the switching threshold varies depending on measurement
strength and can be affected by target distance, color, reflectivity, etc. Use object mode when teaching an object if a
change in state is required when the object is no longer present. Use background mode when teaching background so that
the output state changes when a new object is in front of the background.
Navigate: MENU > Dx_OUT > SPtRef
Remote Input: Not available
Default: Background
L-GAGE
®
LE250/550 Dual Discrete Laser Gauging Sensors
20