Specifications

Supply Voltage and Current

250V ac/dc

Impulse Withstand Voltage

3-position switch:

 2.5 kV

Momentary pushbutton:

 1.5 kV

Output Contact Ratings

See table below.

Rated Thermal Current (Ith):

2.5 A*
*For the following operating temperatures:

40°C < 50°C:

 2 A ( 4 contacts under load)

50°C < 60°C:

 1.5 A ( 3 contacts under load)

Contact Resistance

100 mohm max.

Insulation Resistance

Live to dead metal parts:

 100 Mohm min.

Positive to negative live parts:

 100 Mohm min.

Recommended Wire/Cable Size

Wire:

 0.14 to 1.5 mm² (25 AWG to 16 AWG)

Cable:

 ø 7 to 13 mm

M20 conduit

Short Circuit Protection

250V / 10A fast blow fuse (IEC 60127-1)

Conditional short circuit current:

 50 A (250V)

Vibration Resistance

Operating extremes:

 5 to 55 Hz, half amplitude 0.5

mm minimum

Damage limits:

 16.7 Hz, half amplitude 1.5 mm mini-

mum

Shock Resistance

Operating extremes:

150 m/s² (15 G)

Damage limits:

 1,000 m/s² (100 G)

Direct Opening

(Terminals 5 and 6 models ED1G-L21SM-1N and

ED1G-L21SMB-1N)

Actuating Force:

 70 N minimum

Travel:

 4.7 mm minimum

Date code format:

YYWWX:

 2-digit year, 2-digit week, "X” internal code

Mechanical Life

Positions 1 & 2 only:

 1,000,000 operations minimum

Positions 1, 2 & 3:

 100,000 operations minimum

Operating frequency: 

1,200 operations per hour max-

imum

Electrical Life

100,000 operations minimum at rated load

Pollution Degree

3

Terminal Pulling Strength

20 N minimum

Terminal Screw Torque

0.5 to 0.6 Nm

Operating Conditions (indoor use only)

Temperature:

 –10° to +60° C (no freezing)

Humidity:

 45 to 85% RH max. (no condensation)

Storage Temperature:

 –40° to +80° C (no freezing)

Construction

Polyamide housing and cable gland, NBR/PVC poly-

blend rubber grip switch boot; model 

ED1G-L21SM

-1N

 meets IP66; other models meet IP65

Applicable Standards

Design Standards:

 IEC 60947-5-1, EN 60947-5-1, JIS

C8201-5-1, UL 508, CSA C22.2 No. 14, GS-ET-22

Application Standards:

 ISO 12100/EN ISO 12100,

IEC 60204-1/ EN 60204-1, ISO 11161/EN ISO11161,

ISO10218-1/EN ISO10218-1, ANSI/RIA/ISO 10218-1,

ANSI NFPA 79, ANSI/RIA R15.06, ANSI B11.19, ISO

13849-1/EN ISO 13849-1

Certifications

Ratings approved by Safety Agencies
TÜV rating:

 AC-15 250V ac 0.5A; DC-13 125V dc

0.1A; Applicable EC Directives: LOW Voltage Directive

(2006/95/EC), Machinery Directive (2006/42/EC); Ap-

plicable EC Standard(s): EN60947-5-1, GS-ET-22

UL, c-UL rating:

 250V ac, 0.5A Pilot Duty; 125V dc,

0.1A Pilot Duty, Ambient Tempe40°C, Environ-

mental Rating Type 4X, Indoor Use Only. UL has only

investigated this device for shock and fire to UL508.

 

 

ED1G Enabling Switch

10

www.bannerengineering.com - tel: 763-544-3164

P/N 151822 Rev. B

Summary of Contents for ED1G

Page 1: ...dard ANSI B11 19 Performance Criteria for Safeguards ANSI NFPA 79 2007 and IEC 60204 1 2000 Electrical Re quirements for Industrial Machines Enabling switch left and Enabling switch with integral mome...

Page 2: ...FPA 79 Electrical Standard for Industrial Machinery ANSI RIA R15 06 Safety Requirements for Industrial Robots and Robot Systems ANSI PMMI B155 1 Package Machinery and Packaging Related Converting Mach...

Page 3: ...otherwise be safeguarded Each enabling device must be concurrently operated before machine motion can be initiated The enabling device is not considered to be an emergency stop device but if performin...

Page 4: ...o be bypassed Initiation of motion should only be through a hold to run type of control All emergency stops must remain active The means of bypassing must be employed at the same level of reliability...

Page 5: ...nd must comply with the relevant electrical standards and wiring codes such as the NEC National Electrical Code ANSI NFPA79 or IEC 60204 1 and all applicable local standards and codes Lockout tagout p...

Page 6: ...series connected see wiring diagram and the following warning WARNING Multiple Switching Devices Whenever two or more devices are connected to the same safety module controller Contacts of the corres...

Page 7: ...m L2 27 mm Wire Stripping Length L3 L3 6 mm Terminal No Connector Base L1 L2 L3 L3 Figure 3 Wire lengths to terminal connections 5 Replace the cover and secure with the three screws torque 1 1 to 1 3...

Page 8: ...S21 S22 S12 13 23 33 S31 S32 24 14 34 44 43 A2 S34 S33 Functions requiring bypass Functions not requiring bypass Machine Control Circuits 5 6 1 Selection of the enabling device must be capable of bei...

Page 9: ...the interconnect cabling for crushing cuts or wear 2 Inspect the device for loosening or damage to the mounting hardware or means of storage 3 With the enabling device selected e g bypass or maintenan...

Page 10: ...ons minimum Operating frequency 1 200 operations per hour max imum Electrical Life 100 000 operations minimum at rated load Pollution Degree 3 Terminal Pulling Strength 20 N minimum Terminal Screw Tor...

Page 11: ...esistive load AC 12 2 A 1 A Inductive load AC 15 1 A 0 5 A DC Resistive load DC 12 2 A 0 4 A 0 2 A Inductive load DC 13 1 A 0 22 A 0 1 A Rated Current le Mo mentary push button switch Terminals 7 8 mo...

Page 12: ...p US or e mail Mexico mexico bannerengineering com or Brazil brasil banner engineering com Asia Banner Engineering China Shanghai Rep Office Rm G H I 28th Flr Cross Region Plaza No 899 Lingling Road S...

Reviews: