Parameter
Description
Default value
Unit
Limit Threshold High 1,
Limit Threshold High 2,
Limit Threshold High 3,
Limit Threshold High 4
This parameter specifies the current maximum permissible analog input value.
•
Permissible values: 500 to 25,000 µA (corresponds to 0.5 to 25 mA)
(up to hardware upgrade 1.10.1.0: 3600 to 21,000 µA - corresponds to
3.6 to 21 mA)
20000
µA
Limit Threshold Low 1,
Limit Threshold Low 2,
Limit Threshold Low 3,
Limit Threshold Low 4
This parameter specifies the current minimum permissible analog input value.
•
Permissible values: 500 to 25,000 µA (corresponds to 0.5 to 25 mA)
(up to hardware upgrade 1.10.1.0: 3600 to 21,000 µA - corresponds to
3.6 to 21 mA)
4000
µA
Limit Threshold Equivalent 1,
Limit Threshold Equivalent 2,
Limit Threshold Equivalent 3,
Limit Threshold Equivalent 4
This parameter specifies the maximum permissible deviation between the analog
input values.
•
Permissible values: 0 to 25,000 µA (corresponds to 0 to 25 mA)
(up to hardware upgrade 1.10.1.0: 0 to 21,000 µA - corresponds to 0 to
21 mA)
100
µA
Discrepancy Time 1,
Discrepancy Time 2,
Discrepancy Time 3,
Discrepancy Time 4
This parameter specifies the maximum time for the "Dual-channel evaluation"
function in which the difference between both analog input values is permitted
to exceed the limit value.
•
Permissible values: 0 to 10,000 ms (corresponds to 0 to 10 s)
0
ms
Table 20: SafeDESIGNER parameters: SafeCurrentxxyy
The parameters "Limit Threshold High x", "Limit Threshold Low x", "Limit Threshold Equivalent x" and
"Discrepancy Time x" together make up a parameter set. The channels "SafeThrSelector_xxyy_Bit1" and
"SafeThrSelector_xxyy_Bit2" are available in the SafeDESIGNER application to determine which parameter set in
the module is enabled, i.e. it is possible to change the parameter set at runtime.