X20 system modules • Digital output modules • X20DO8232
1236
X20 system User's Manual 3.10
4.15.22.4 Status LEDs
Figure
LED
Color
Status
Description
Off
Module supply not connected
Single flash
Reset mode
Blinking
PREOPERATIONAL mode
r
Green
On
RUN mode
Off
Module supply not connected or everything OK
Single flash
Warning/Error on an I/O channel. Level monitoring for digital outputs has been
triggered.
e
Red
Double flash
External I/O supply is outside the valid range: 12 VDC (-15% / +20%)
e + r
Red on / Green single flash
Invalid firmware
1 - 8
Orange
Output status of the corresponding digital output
Table 397: Status LEDs
4.15.22.5 Pinout
1
X
20
D
O
8
23
2
2
DO 1
DO 3
DO 5
DO 2
DO 4
DO 6
DI 1
GND
GND
DO 7
+12 VDC
DO 8
+12 VDC
3 4
3 4
5 6
5 6
7 8
r
e
Figure 372: Pinout
4.15.22.6 Connection example
DO
Actuator 5
Actuator 7
Actuator 3
Actuator 1
Actuator 6
Actuator 8
Actuator 4
Actuator 2
+12 V ext.
GND
_
+
Figure 373: Connection example
Caution!
If the module is operated outside of specifications, the output current can increase above the maximum
permissible nominal current. This applies to individual channels and also to the summation current
for the module.
Therefore sufficient cable cross sections or external safety measures must be used.
Summary of Contents for X20 System