28
Scranton, IA 51462
Phone (712) 652-3424
www.bdmfginc.com
Model BDAH-04
Heating Data
CFM
P.D.
(Ft. H2O)
GPM
105°F Entering Water
110°F Entering Water
115°F Entering Water
70°F Entering Air
70°F Entering Air
70°F Entering Air
Total MB/H
Exit H2O°F
Total MB/H
Exit H2O°F
Total MB/H
Exit H2O°F
Heating
Capacities b
ased
up
on
0%
Gl
ycol
1400
2.1
6
41.4
91.1
47.5
94
53.5
97
5.5
10
46.1
95.7
52.7
99.3
59.4
103
1500
2.1
6
43
90.6
49.2
93.4
55.5
96.3
5.5
10
48.2
95.3
55.2
98.8
62.2
102.4
1600
2.1
6
44.4
90.1
50.9
92.9
57.4
95.7
5.5
10
50.3
94.9
57.6
98.4
64.9
101.9
1750
2.1
6
46.3
89.4
53.1
92.2
59.9
94.9
5.5
10
53.1
94.3
60.8
97.7
68.7
101.2
Heating
Cap
acities
b
ased
up
on
10
% Gly
col
1400
2.3
6
39.7
91.5
45.7
94.5
51.8
97.4
5.8
10
45.1
95.8
51.7
99.5
58.3
103.1
1500
2.3
6
41.1
91.1
47.3
94
53.6
96.8
5.8
10
47.2
95.4
54.1
99
61
102.6
1600
2.3
6
42.4
90.6
48.8
93.5
55.3
96.2
5.8
10
49.1
95
56.3
98.6
63.5
102.1
1750
2.3
6
44
90.1
50.7
92.8
57.5
95.5
5.8
10
51.7
94.5
59.4
97.9
66.9
101.4
Heating
Cap
acities
b
ased
up
on
20
% Gly
col
1400
2.4
6
37.3
92.2
43
95.2
48.8
98.2
6.1
10
43.7
96
50.2
99.7
56.8
103.3
1500
2.4
6
38.5
91.8
44.4
94.7
50.4
97.7
6.1
10
45.5
95.6
52.4
99.2
59.3
102.8
1600
2.4
6
39.6
91.4
45.7
94.3
51.9
97.2
6.1
10
47.3
95.3
54.4
98.8
61.6
102.3
1750
2.4
6
41
90.9
47.4
93.7
53.8
96.5
6.1
10
49.6
94.8
57.1
98.2
64.8
101.7
Electric Heat Strip Information
PART#
DESCRIPTION
AH10KWHEAT
10KW ELECTRIC STRIP HEAT
AH15KWHEAT
15KW ELECTRIC STRIP HEAT
Electric Heat Strip Capacities
KW
BTU/H
TOTAL AMPS
240V
208V
240V
208V
240V
208V
10KW
7.51KW 34100 BTU/H 25609 BTU/H 41.7 AMPS 36.1 AMPS
15KW
11.3KW 51150 BTU/H 38533 BTU/H 62.5 AMPS 54.3 AMPS
NOTE:
The above listed heat strip part numbers and heat strip capacities data is only for the HSS
®
Air Handlers. These
are specially designed for the electrical heat strip units for
B&D Mfg., Inc.
The electrical heat strip units are factory
installed if ordered with electrical heat strip and can be field installed also if ordered without electrical heat strip.