1.  This equipment shall be connected directly to the DC supply system 

earthed electrode conductor or to a bonding jumper from a grounded 
terminal bar or bus to which the DC supply system grounding electrode 
conductor is connected. 

2.  This equipment shall be located in the same immediate area (such as, 

adjacent cabinets) as any other equipment that has a connection 
between the earthed conductor of the same DC supply circuit and the 
earthing conductor, and also the point of earthing of the DC system.  
The DC system shall not be earthed elsewhere. 

3.  The DC supply source shall be located within the same premises as this 

equipment. 

4.  Switching or disconnecting devices shall not be in the earthed circuit 

conductor between the DC source and the point of connection of the 
earthing electrode conductor. 

Rack Mount Precautions 

1.  Elevated Operating Ambient - If installed in a closed or multi-unit rack 

assembly, the operating ambient temperature of the rack environment 
may be greater than room ambient. Therefore, consideration should be 
given to installing the equipment in an environment compatible with the 
maximum ambient temperature (Tma) specified by the manufacturer.  

2.  Reduced Air Flow - Installation of the equipment in a rack should be 

such that the amount of air flow required for safe operation of the 
equipment is not compromised.  

3.  Mechanical Loading - Mounting of the equipment in the rack should be 

such that a hazardous condition is not achieved due to uneven 
mechanical loading.  

4.  Circuit Overloading - Consideration should be given to the connection 

of the equipment to the supply circuit and the effect that overloading of 
the circuits might have on overcurrent protection and supply wiring. 
Appropriate consideration of equipment nameplate ratings should be 
used when addressing this concern.  

5.  Reliable Earthing - Reliable earthing of rack-mounted equipment 

should be maintained. Particular attention should be given to supply 
connections other than direct connections to the branch circuit (e.g. 
use of power strips). 

 

4

 

Summary of Contents for IE-MediaChassis/2

Page 1: ...IE MediaChassis 2 DC Operation Manual...

Page 2: ...iginal user and is not transferable This warranty is expressly conditioned upon proper storage installation connection operation and maintenance of products in accordance with their written specificat...

Page 3: ...THE INTELLECTUAL PROPERTY RIGHTS OF ANY THIRD PARTY IN NO EVENT SHALL B B ELECTRONICS BE LIABLE FOR LOSS OF BUSINESS LOSS OF USE OR OF DATA INTERRUPTION OF BUSINESS LOST PROFITS OR GOODWILL OR OTHER...

Page 4: ...ssis 2 DC 1 Installing the IE MediaChassis 2 DC 1 Configuring and Installing Modules 3 DC Power Supply Wiring Instructions 3 Rack Mount Precautions 4 DC Power Supply Precautions 5 B B Electronics Tech...

Page 5: ...ncludes a temperature triggered fan When the internal temperature of the chassis reaches 86 F 30 C the fan is activated As the temperature increases the fan drive duty cycle adjusts to increase the fa...

Page 6: ...ires a rackmount shelf for mounting up to three units side by side 3 If mounting the chassis on a wall place two 10 panhead screws not supplied on the wall the distance of the holes on the chassis and...

Page 7: ...ystem application For positive ground system applications remove the chassis ground shorting jumper and connect it between the positive terminal and the chassis ground terminal Alternatively the chass...

Page 8: ...erating ambient temperature of the rack environment may be greater than room ambient Therefore consideration should be given to installing the equipment in an environment compatible with the maximum a...

Page 9: ...b Route input wiring to terminal block and secure in such a manner that it is protected from damage and stress Do not route wiring past sharp edges or moving parts c Incorporate a readily accessible...

Page 10: ...92444 Fax 353 91 792445 Website www bb europe com Specifications Environmental Operating Temperature 31 F to 156 2 F 35 C to 69 C Storage Temperature 67 F to 257 F 55 C to 125 C Humidity 5 to 95 non c...

Page 11: ...aintain grounded contact with the system unit throughout any procedure requiring ESD protection 3 Hold boards by the edges only do not touch the electronic components or gold connectors 4 After remova...

Page 12: ...C WEEE requires that any equipment that bears this symbol on product or packaging must not be disposed of with unsorted municipal waste This symbol indicates that the equipment should be disposed of s...

Page 13: ...without notice B B Electronics assumes no responsibility for any errors that may appear in this document IE MediaChassis 2 is a trademark of B B Electronics Other brands or product names may be trade...

Reviews: