DESCRIPTION OF OPERATION WITH LIQUID
FUEL
FURTHER INSTRUCTIONS TO START A MIXED BURNER
It is advisable to perform the first ignition with liquid fuel (switch 2
in ON position, Oil led comes on) because in this case delivery is
conditioned by the available nozzle, whereas the delivery of methane
can be varied as you like by adjusting its flow-rate regulator.
It is not advisable to have too large a burner for the boiler for heating
and for hot water as the burner may work for long periods with a
single flame, making the boiler work at lower than required output; as
a result of this the combustion products (fumes) emerge at too low a
temperature (at about 180°C in the case of heavy oil and 130°C with
diesel fuel), causing soot to build up at the chimney outlet.
When the two-flame burner is installed on a water boiler for heating
use, it must be connected so that it works normally with both flames,
completely stopping without passing to the first flame when the preset
temperature is reached.
To obtain this operating condition, do not install the second flame
thermostat and make a direct connection (bridge) between the
respective four pole plug terminals.
In this way only the burner’s capacity to switch on at low rate is used
for a gentle ignition, which is essential for boilers with a pressurised
combustion chamber and also very useful for normal boilers with
depression combustion chamber. The burner (start/stop) command is
subject to the usual operating or safety thermostats.
The motor turns the fan that carries out an air wash of the combustion
chamber and, at the same time, the fuel pump that causes circulation
in the ducts, expelling any gas bubbles through the return valve. This
pre-wash stage ends with the opening of the safety and first stage
solenoid valves, which allows the fuel at a pressure of 12 bar to get to
the first stage nozzle and from this to enter the combustion chamber
finely atomised.
As soon as the atomized fuel exits the nozzle, it is set on fire by the
spark present between the electrodes since the start of the motor.
During first stage ignition, the air gate is held in the adjusted position
on the special air/gas adjustment servomotor cam.
If the flame appears regularly, after the safety time foreseen by the
device, it starts the air/gas regulation servomotor that moves to the
second stage position. During the transition from the first to the
second stage, the servo motor operates the solenoid valve (normally
closed) of the second stage.
The control equipment follows the program and switches the ignition
transformer off. When the temperature or the pressure in the boiler
reaches that set by the thermostat or pressure switch, the latter stops
the burner.
Subsequently, if the temperature of pressure decreases below the
lower thermostat or pressure switch threshold value, the burner will
switch on again.
If, for any reason, the flame fails during operation, after just one
second the flame control device cuts off the power supply to the relay,
causing the deactivation of the solenoid valves which intercept the
fuel flow to the nozzles.
The ignition phase is repeated in this manner and, if the flame
reignites normally, the burner will return to normal operation.
Otherwise (irregular flame or no flame), the equipment will shut-down
automatically.
If the program is interrupted (power failure, manual intervention,
thermostat intervention, etc...) during the prewashing phase the
programmer will return to its initial position and will automatically
repeat the entire burner ignition phase.
CAUTION / WARNING
The selection of the nozzles in relation to the desired total
flow rate (2 nozzles in operation) must be made taking into
consideration the flow rate values that correspond to the
diesel operating pressure of 12 bar. Replacing the nozzles it is
possible to vary greatly the relationship between the first and
the second stage.
2
4
1
3
7
tar
ghetta.jpg
1) Main switch ON- OFF
2) Liquid fuel operation indicator light
3) Fuel switch
4) Gas warning light
7) Equipment lock light / equipment release button
Summary of Contents for TBML 60P
Page 2: ......
Page 4: ...ITALIANO 2 42 0006160060_201802 ITALIANO Schemi elettrici 41...
Page 43: ...ITALIANO 41 42 0006160060_201802 SCHEMI ELETTRICI...
Page 46: ...ENGLISH 2 42 0006160060_201802 ENGLISH Wiring diagrams 41...
Page 85: ...ENGLISH 41 42 0006160060_201802 WIRING DIAGRAMS...
Page 87: ......