ENGLISH
9 / 42
0006160060_201802
¹) NATURAL GAS EMISSIONS
Classes defined according to Standard EN 676.
Class
NOx emissions in mg/kWh - natural
gas
1
≤ 170
2
≤ 120
3
≤ 80
²) PROPANE EMISSIONS
CO emissions, natural gas/propane ≤ 100 mg/kWh
Class
NOx emissions in mg/kWh - propane
gas
1
≤ 230
2
≤ 180
3
≤ 140
³) DIESEL EMISSIONS
Classes defined according to Standard EN 267.
Class
NOx emissions in mg/
kWh - diesel fuel
CO emissions in mg/
kWh - diesel fuel
1
≤ 250
≤ 110
2
≤ 185
≤ 110
3
≤ 120
≤ 60
OPERATING RANGE
IMPORTANT
The working fields are obtained from test boilers corresponding to the standard EN267 for liquid fuels and EN676 for gas fuels and are
indicative for the combination burner-boiler. For correct working of the burner, the size of the combustion chamber must correspond to
current regulations; if not the manufacturers must be consulted.
The burner should not work outside the indicated work range.
Summary of Contents for TBML 60P
Page 2: ......
Page 4: ...ITALIANO 2 42 0006160060_201802 ITALIANO Schemi elettrici 41...
Page 43: ...ITALIANO 41 42 0006160060_201802 SCHEMI ELETTRICI...
Page 46: ...ENGLISH 2 42 0006160060_201802 ENGLISH Wiring diagrams 41...
Page 85: ...ENGLISH 41 42 0006160060_201802 WIRING DIAGRAMS...
Page 87: ......