EXPECTED LIFESPAN
The expected lifespan of burners and relevant components depends very much from the type of application on which the burner is installed, from
cycles ,of delivered power, from the conditions of the environment in which it is located, from maintenance frequency and mode, etc.
Standards about safety components provide for a project expected lifespan expressed in cycles and/or years of operation.
Such components ensure the correct operation in standard (*) operating conditions, with periodic maintenance according to the instructions
contained in the manual.
The table below shows the project expected lifespan of the main safety components; approximately, operating cycles correspond to the burner
activations.
When this expected lifespan limit has almost been reached the component must be replaced with an original
spare part
.
IMPORTANT
warranty conditions (laid down in contracts and/or delivery or payment notes, if necessary) are independent and do not refer to the
expected lifespan stated below.
(*) “Normal” operating conditions means applications on water boilers and steam generators or industrial applications compliant with the standard
EN 746-2 in environments with temperatures within the limits provided for in this manual and with pollution degree 2 in compliance with annex
M of the standard EN 60204-1.
Safety component
Project expected lifespan
Operating cycles
Years of operation
Control box
250.000
10
Flame sensor (1)
n.a.
10,000 operating hours
Seal control
250.000
10
Gas pressure switch
50.000
10
Air pressure switch
250.000
10
Gas pressure regulator (1)
n.a.
15
Gas valves (with seal check)
Until the first seal fault signal
Gas valves (without seal check) ( 2)
250.000
10
Servomotors
250.000
10
Liquid fuel hoses
n.a.
5 (every year for fuel oil burners or in the presence of
biodiesel in diesel/kerosene)
Liquid fuel valves
250.000
10
Air fan impeller
50,000 activations
10
(1) The characteristics can degrade over time; during the annual maintenance the sensor must be checked and in case of flame signal degra
-
dation must be replaced.
(2) Using normal mains gas.
32 / 42
0006160409_202305
ENGLISH
Summary of Contents for TBML 2000 ME
Page 2: ......
Page 38: ...SCHEMI ELETTRICI TBML 1200ME 1600ME 2000ME BT 335 36 42 0006160409_202305 ITALIANO...
Page 39: ...TBML 1200ME 1600ME 2000ME BT 335 37 42 0006160409_202305 ITALIANO...
Page 40: ...TBML 1200ME 1600ME 2000ME BT 335 38 42 0006160409_202305 ITALIANO...
Page 41: ...TBML 1200ME 1600ME 2000ME BT 335 39 42 0006160409_202305 ITALIANO...
Page 42: ...BA I1 I2 I3 I4 TBML 1200ME 1600ME 2000ME BT 335 40 42 0006160409_202305 ITALIANO...
Page 44: ...42 42 0006160409_202305 ITALIANO...
Page 80: ...WIRING DIAGRAMS TBML 1200ME 1600ME 2000ME BT 335 36 42 0006160409_202305 ENGLISH...
Page 81: ...TBML 1200ME 1600ME 2000ME BT 335 37 42 0006160409_202305 ENGLISH...
Page 82: ...TBML 1200ME 1600ME 2000ME BT 335 38 42 0006160409_202305 ENGLISH...
Page 83: ...TBML 1200ME 1600ME 2000ME BT 335 39 42 0006160409_202305 ENGLISH...
Page 84: ...BA I1 I2 I3 I4 TBML 1200ME 1600ME 2000ME BT 335 40 42 0006160409_202305 ENGLISH...
Page 86: ...42 42 0006160409_202305 ENGLISH...
Page 87: ......