![baltur TBG 900 ME Instruction Manual For Installation, Use And Maintenance Download Page 51](http://html.mh-extra.com/html/baltur/tbg-900-me/tbg-900-me_instruction-manual-for-installation-use-and-maintenance_470482051.webp)
MAINTENANCE TIME
Part description
Action to be performed
Gas
COMBUSTION HEAD
ELECTRODES
VISUAL INSPECTION OF THE INTEGRITY OF CERAMICS. TIP GRINDING, CHECK DISTANCE, CHECK
ELECTRICAL CONNECTION
YEARLY
FLAME DISC
INTEGRITY VISUAL CHECK FOR ANY DEFORMATIONS, CLEANING,
YEARLY
IONISATION PROBE
VISUAL INSPECTION OF THE INTEGRITY OF CERAMICS. TIP GRINDING, CHECK DISTANCE, CHECK
ELECTRICAL CONNECTION
YEARLY
COMBUSTION HEAD COMPO-
NENTS
INTEGRITY VISUAL CHECK FOR ANY DEFORMATIONS, CLEANING,
YEARLY
INSULATING GASKET
SEAL VISUAL INSPECTION AND POSSIBLE REPLACEMENT
YEARLY
GAS DELIVERY COUPLING SEAL
SEAL VISUAL INSPECTION AND POSSIBLE REPLACEMENT
YEARLY
AIR LINE
AIR GRILLE/DAMPERS
CLEANING
YEAR
AIR DAMPER BEARINGS
GREASING, (Note: apply only on burners with bearings requiring lubrication)
YEAR
FAN
FAN AND SCROLL CLEANING, DRIVE SHAFT GREASING
YEAR
AIR PRESSURE SWITCH
CLEANING
YEAR
AIR PRESSURE PORT AND PIPES
CLEANING
YEAR
SAFETY COMPONENTS
FLAME SENSOR
CLEANING
YEAR
GAS PRESSURE SWITCH
FUNCTIONAL INSPECTION
YEAR
VARIOUS COMPONENTS
ELECTRIC MOTORS
COOLING FAN CLEANING, BEARING NOISE CHECK
YEAR
MECHANICAL CAM
CHECK OF WEAR AND OPERATION, GREASING OF SLIDING BLOCK AND SCREWS
YEAR
LEVERS/TIE-RODS/BALL JOINTS
CHECK OF ANY WEAR, COMPONENT LUBRICATION
YEAR
ELECTRICAL SYSTEM
CHECK OF CONNECTIONS AND TERMINAL TIGHTENING
YEAR
INVERTER
COOLING FAN CLEANING AND TERMINAL TIGHTENING
YEAR
CO PROBE
CLEANING AND CALIBRATION
YEAR
O2 PROBE
CLEANING AND CALIBRATION
YEAR
COMBUSTION HEAD EXTRACTION
KIT
CHECKING WEAR AND OPERATION
YEAR
FUEL LINE
GAS FILTER
REPLACING THE FILTERING ELEMENT
YEAR
HYDRAULIC/GAS SEALS
CHECK OF ANY LEAKAGES
YEAR
COMBUSTION PARAMETERS
CO CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
CO2 CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
BACHARACH SMOKE INDEX
CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
n.a.
NOX CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
IONISATION CURRENT CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
SMOKE TEMPERATURE CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
GAS PRESSURE REGULATOR
PRESSURE MEASURED AT START-UP
YEAR
IMPORTANT
In case of heavy-duty operation or when using special fuels, the maintenance intervals must be reduced adapting them to the real opera
-
ting conditions, according to the indications of the maintenance technician.
21 / 28
0006160267_202106
ENGLISH
Summary of Contents for TBG 900 ME
Page 2: ......
Page 26: ...SCHEMI ELETTRICI TBG 800 ME 900 ME 2000 ME 24 28 0006160267_202106 ITALIANO ...
Page 27: ...TBG 800 ME 900 ME 2000 ME 25 28 0006160267_202106 ITALIANO ...
Page 28: ...TBG 800 ME 900 ME 2000 ME 26 28 0006160267_202106 ITALIANO ...
Page 29: ...TBG 800 ME 900 ME 2000 ME I1 I2 BA I4 I3 27 28 0006160267_202106 ITALIANO ...
Page 54: ...WIRING DIAGRAMS TBG 800 ME 900 ME 2000 ME 24 28 0006160267_202106 ENGLISH ...
Page 55: ...TBG 800 ME 900 ME 2000 ME 25 28 0006160267_202106 ENGLISH ...
Page 56: ...TBG 800 ME 900 ME 2000 ME 26 28 0006160267_202106 ENGLISH ...
Page 57: ...TBG 800 ME 900 ME 2000 ME I1 I2 BA I4 I3 27 28 0006160267_202106 ENGLISH ...
Page 59: ......