Install a suitable disconnecting switch and protection fuses for each
power supply line of the burner, following the indications in the
diagram on the side and in the table 2.
Sezionatore_fusibili
fig2
PROTECTION WITH DISCONNECTING SWITCH AND FUSES
TABLE 2
Connection 3~400V and 1+N ~230V 50 Hz
TBG 450 ME
TBG 510 ME
TBG 650 ME
TBG 750 ME
1~230V 50
Hz
3~400V 50
Hz
1~230V 50
Hz
3~400V 50
Hz
1~230V 50
Hz
3~400V 50
Hz
1~230V 50
Hz
3~400V 50
Hz
Motor connection
-
Y
-
Y
-
Δ/Y
-
Δ/Y
Motor nom curr
A
-
16.5 A
-
19.9 A
-
26.8 A
-
33 A
Motor thermal protection calibration (F1)
A
-
18 A
-
22 A
-
17 A
-
21 A
Connection line minimum section (S1, S2) 4) sq.mm
1,5
4
1,5
6
1,5
10
1,5
10
Disconnecting pole number
1+N
3
1+N
3
1+N
3
1+N
3
Fuse size 5)
A
6
50
6
63
6
50
6
63
Fuse type
gG
gG
gG
gG
gG
gG
gG
gG
Ultimate rated short-circuit breaking capacity
(Icu)
kA
≥ 100
≥ 100
≥ 100
≥ 100
≥ 100
≥ 100
≥ 100
≥ 100
Fuse intervention time Ti 6)
sec
0,2
0,07
0,2
0,07
0,2
0,07
0,2
1
Fuse intervention time Ti 7)
sec
5
5
5
5
5
5
5
5
4)
Sections S1 and S2 are calculated for PVC insulated copper conductors, class 5 or higher, at an ambient temperature of 40° C, considering single cables
placed side by side and not wound. Provide for any downgrades in case of different conditions.
The sections of connection cables must be chosen based on the distance from the connection point so that the voltage drop at the burner panel terminals
does not exceed 4% with respect to the nominal value.
5)
The protection devices against overcurrents have been calculated at an ambient temperature of 30° C. Provide for any downgrades in case of different
conditions.
6)
TT SYSTEMS:
Ti - 0.2 s (230V single-phase)
Ti - 0.07 s (400V three-phase) for I<32A
Ti - 1 s (400V three-phase) for I>32A
7)
TN SYSTEMS:
Ti - 5 s (230V single-phase and 400V three-phase)
18 / 44
0006160281_202201
ENGLISH
Summary of Contents for TBG 450LX ME
Page 2: ......
Page 34: ...SCHEMI ELETTRICI 32 44 0006160281_202201 ITALIANO...
Page 35: ...33 44 0006160281_202201 ITALIANO...
Page 36: ...34 44 0006160281_202201 ITALIANO...
Page 37: ...BA BP I1 I2 I3 I4 35 44 0006160281_202201 ITALIANO...
Page 38: ...36 44 0006160281_202201 ITALIANO...
Page 39: ...37 44 0006160281_202201 ITALIANO...
Page 40: ...38 44 0006160281_202201 ITALIANO...
Page 41: ...39 44 0006160281_202201 ITALIANO...
Page 42: ...40 44 0006160281_202201 ITALIANO...
Page 43: ...BA BP I1 I2 I3 I4 41 44 0006160281_202201 ITALIANO...
Page 44: ...42 44 0006160281_202201 ITALIANO...
Page 45: ...43 44 0006160281_202201 ITALIANO...
Page 78: ...WIRING DIAGRAMS 32 44 0006160281_202201 ENGLISH...
Page 79: ...33 44 0006160281_202201 ENGLISH...
Page 80: ...34 44 0006160281_202201 ENGLISH...
Page 81: ...BA BP I1 I2 I3 I4 35 44 0006160281_202201 ENGLISH...
Page 82: ...36 44 0006160281_202201 ENGLISH...
Page 83: ...37 44 0006160281_202201 ENGLISH...
Page 84: ...38 44 0006160281_202201 ENGLISH...
Page 85: ...39 44 0006160281_202201 ENGLISH...
Page 86: ...40 44 0006160281_202201 ENGLISH...
Page 87: ...BA BP I1 I2 I3 I4 41 44 0006160281_202201 ENGLISH...
Page 88: ...42 44 0006160281_202201 ENGLISH...
Page 89: ...43 44 0006160281_202201 ENGLISH...
Page 91: ......