FLAME DETECTION CURRENT
The minimum ionisation current needed to run the equipment is 3
µA.The burner flame generates a significantly higher current, which
usually does not require any control by the equipment.Should the
ionisation current need to be measured, a microammeter must be
connected in series to the ionisation electrode lead by opening the
connector “C”, see wiring diagram.
DIAGRAM FOR REGULATING THE COMBUSTION HEAD AND THE ELECTRODE DISK DISTANCE
0002935683_TBG35
TBG 35
E
1 - Ionisation electrode
2 - Ignition electrode
3 - Flame disc
4 - Mixer
5 - Gas delivery pipe
E - WARNING: nozzle hole outlet near the electrode tip.
A
B
C
D
TBG 35 / 35P
4
5
4
4