ELECTRICAL CONNECTIONS
•
It is advisable to make all connections with flexible electric wire.
•
Conductor cross-sections not specified are to be considered as
0,75 mm².
•
The power lines must be distanced from the hot parts.
•
The burner can be installed exclusively in environments with
pollution degree 2 as specified in Standard EN 60204-1.
•
Make sure that the power line frequency and voltage values
comply with those mentioned in the plate.
•
The three-phase or single-phase power supply line must have a
circuit breaker with fuses.
•
The regulations further require a switch on the burner power
supply line, to be positioned outside the boiler room and easily
accessible.
•
The main line and relevant switch with fuses must be suitable to
support the maximum current absorbed by the burner.
•
A single-pole switch with a contact opening gap equal or above
3 mm is required for the mains supply connection, in accordance
with current safety regulations.
•
Refer to the wiring diagram for electrical connections (line and
thermostats).
•
Strip the outer insulation of the power cable just as necessary for
the connection, preventing the cable to touch metal parts, and
provide a longer length for the earth conductor.
CAUTION / WARNINGS
Only professionally qualified personnel may open the burner
electrical switchboard.
13 / 32
0006160502_202306
ENGLISH
Summary of Contents for TBG 2000 LX ME
Page 2: ......
Page 28: ...SCHEMI ELETTRICI 26 32 0006160502_202306 ITALIANO...
Page 29: ...27 32 0006160502_202306 ITALIANO...
Page 30: ...28 32 0006160502_202306 ITALIANO...
Page 31: ...29 32 0006160502_202306 ITALIANO...
Page 32: ...30 32 0006160502_202306 ITALIANO...
Page 34: ...32 32 0006160502_202306 ITALIANO...
Page 60: ...WIRING DIAGRAMS 26 32 0006160502_202306 ENGLISH...
Page 61: ...27 32 0006160502_202306 ENGLISH...
Page 62: ...28 32 0006160502_202306 ENGLISH...
Page 63: ...29 32 0006160502_202306 ENGLISH...
Page 64: ...30 32 0006160502_202306 ENGLISH...
Page 66: ...32 32 0006160502_202306 ENGLISH...
Page 67: ......