TECHNICAL SPECIFICATIONS
MODEL
TBG 120 P
TBG 150 P
TBG 210 P
MAXIMUM NATURAL GAS HEAT POWER
kW
1200
1500
2100
MINIMUM NATURAL GAS HEAT POWER
kW
240
300
400
¹) NATURAL GAS EMISSIONS
mg/kWh
Class 2
Class 2
Class 2
OPERATION
TWO-STAGE
TWO-STAGE
TWO-STAGE
NATURAL GAS TRANSFORMER 50 Hz
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
NATURAL GAS TRANSFORMER 60 Hz
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
MAXIMUM NATURAL GAS HEAT RATE
Stm³/h
127
158.7
222.2
MINIMUM NATURAL GAS HEAT RATE
Stm³/h
25.4
31.7
42.3
MAXIMUM NATURAL GAS PRESSURE
hPa (mbar)
360
350
350
NATURAL GAS MINIMUM PRESSURE
hPa (mbar)
20
21.7
30
PROPANE GAS MAXIMUM THERMAL POWER
kW
1351
1859
2114
PROPANE GAS MINIMUM THERMAL POWER
kW
207
167
271
PROPANE GAS MAXIMUM HEAT CAPACITY
Stm³/h
55.3
76.1
86.5
PROPANE GAS MINIMUM HEAT CAPACITY
Stm³/h
8.5
6.8
11.1
PROPANE GAS MAXIMUM PRESSURE
hPa (mbar)
360
350
350
²)PROPANE EMISSIONS
mg/kWh
Class 2
Class 2
Class 2
50 Hz FAN MOTOR
kW
1.5
2.2
3
60Hz FAN MOTOR
kW
1.5
2.6
3.5
ABSORBED ELECTRICAL POWER* 50Hz
kW
1.6
2,40
3.2
ABSORBED ELECTRICAL POWER* 60Hz
kW
1.6
2.8
3.7
50 Hz POWER SUPPLY VOLTAGE
3N~ 400V ± 10%
3N~ 400V ± 10%
3N~ 400V ± 10%
60 Hz POWER SUPPLY VOLTAGE
3N~ 380V ± 10%
3N~ 380V ± 10%
3N~ 380V ± 10%
DEGREE OF PROTECTION
IP54
IP54
IP54
FLAME DETECTOR
IONISATION PROBE
IONISATION PROBE
IONISATION PROBE
EQUIPMENT
LME 22..
LME 22..
LME 22..
AIRFLOW REGULATION
MECHANICAL CAM
MECHANICAL CAM
MECHANICAL CAM
WEIGHT WITH PACKING
kg
87
91
94
CO emissions, natural gas/propane ≤ 100 mg/kWh
Calorific power lower than reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9.45 kWh/Stm³ = 34.02 MJ/Stm³
Propane gas: Hi = 24.44 kWh/Stm³ = 88.00 MJ/Stm³
For different types of gas and pressure values, please contact our sales department.
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
* Total absorption at start with ignition transformer on.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory
environment conditions and cannot be compared to measurements carried out in different locations.