0006080095_200902
SQN 30.111 A3500
- PREVENTILATION WITH AIR OPEN (2nd FLAME POSITION) AIR CLOSED WITH BURNER IN STOP POSITION
In order to modify the cams regulation it’s necessary to intervene on the relative red rings. Pushing by sufficient strength,in the sens one
desires, each red ring can turn in respect to the reffering scale. The pointer of the red ring indicates on the respective reffering scale the
rotation angle set for each cam.
1 - 2nd Flame valve connection cam (must be adjusted in a position between the 1st flame and the 2nd flame cam)
2 - Air regulation cam 1° flame
3 - Close air shutter cam with burner in stop position
4 - Air regulation cam 2nd flame
2
3
4
1
Motor-cam shaft coupling cutting out pin.
The switching-off of the motor and shaft connection can be
obtained by pushing.
N° 8653-1
rev. 09/04/87