ENGLISH
56 / 62
0006081528_201711
BLOCK DIAGRAM ILLUSTRATING THE PRINCIPLE OF L.P.G. PRESSURE REDUCTION IN TWO STAGES FOR BURNER OR BOILER
Pressure gauge and pressure
intake
LPG tank
1st step reducer
Output ~ 1.5 bar
Flow rate ~ double the maximum required by the
user
2nd step reducer
Output ~ 30 hPa (mbar)
Flow rate ~ double the maximum required by
the user
Y filter
Filter
Filter
Pressure intake
2nd step reducer
Output ~ 30 hPa (mbar)
Flow rate ~ double the maximum required by
the user
Y filter
Ball cock
Vibration-proof
joint
Burner
Free-standing or wall-mounted
boiler
Pipe fitting
SUPPLIED BY THE MANUFACTURER
TO BE CARRIED OUT BY THE INSTALLER
Summary of Contents for btg 20 me
Page 2: ......
Page 29: ...ITALIANO 29 32 0006081528_201711 SCHEMI ELETTRICI...
Page 30: ...ITALIANO 30 32 0006081528_201711...
Page 31: ...ITALIANO 31 32 0006081528_201711...
Page 59: ...ENGLISH 59 62 0006081528_201711 WIRING DIAGRAMS...
Page 60: ...ENGLISH 60 62 0006081528_201711...
Page 61: ...ENGLISH 61 62 0006081528_201711...
Page 63: ......