CONNECTRON AIR MOTOR LKS 300
REGULATION

N° 8639

Rev. 10/05/00

To regulate please do as follows:

A) open the thermostats’ circuit (disconnect the connection thermostats lcable)

B) give voltage to the burner by closing the switches on the feeding line and the one on the burner. The control

box must not, be in “lock position”, the control box fuse must be correctly at work and the cyclic relay must
be stand in start position.

ATTENTION : the following operations must be done with circuits under voltage, pay the utmost attention

when operating.

C) with the burner in above described conditions, act on the regulation screw of the cam “O” to obtain the comple-

te closing of the air shutter. In this position “O” cam must push on the relative micro-switch. Releasing the
screw, the air shutter moves towards closure. If the “close” position is overcome, the shutter opens in the op-
posite sense of the requested one (to remedy, tighten adequately the regulation screw and soon after let the
shutter open temporarily, by operating as described at point ”E”). This position (closed shutter with burner at a
stand) is usually already regulated at factory. We remember once again that not all burners are equipped with
an electric circuit suitable to use this cam (see Note).

ATTENTION : the cam step MUST NOT GO further the position which causes the micro switch to get into

operation. If the micro-switch has not come to operation, the burner’s control box stops in the “pre-
washing” position.

D) air regulation 1st stage (cam “ST1”).

Disconnect the cable connected to the buckle N° 9 of the junction box of LKS 300 and connect it temporarily
to the buckle N° 3. Operating on the regulation screw of “ST1” cam, the displacement of the air shutter in the
desired position can be obtained. By screwing the air shutter opens, by releasing the air shutter closes.

E) air regulation 2nd stage (cam “ST2”).

Disconnect temporarily the cable connected to buckle N° 3 (the same which was previously disconnected
from buckle N° 9) and connect it temporarily to the buckle N°7.
Operating on the regulation screw of “ST2” cam it can be obtained the air shutter displacement on the desired
position. By screwing the air shutter opens, by releasing the air shutter closes.

F) Return the temporarily disconnected wire to its terminal (No. 9).

G) The position of cam “MV2”, which controls activation of the second stage fuel valve, can be adjusted by means

of the adjuster screws. The adjustment is usually carried out at the factory in the intermediate position between
ST1” and “ST2”.

NOTE: The cam “MV2” is integral with the “ST2”; therefore, modifying the adjustment of the latter (“ST2”)

also modifies the position of “MV2”.

H) Thus, after pre-adjustment of the position of the air damper, proceed with lighting the burner and adjusting the

combustion air supply for the 1

st

 and 2

nd

 stages. Remember that slackening the cam adjuster screws will cause

the air damper to close, and vice-versa.

N.B.:

1) When the wires coming from the outside of the LKS 300 motor are not connected to terminals 7-8-9 and 10 of the

motor, the electric circuit of the burner in question is not set for using cam “O”. In this condition, it is obviously
unnecessary to adjust this cam (“O”) because it is not operative, so its position is indifferent for the working of the
burner. In this case, during the pre-ventilation and stop of the burner, the air damper automatically sets itself in the
position corresponding to the 1

st

 flame.

2) When the wires coming from the outside of the LKS 300 motor are connected to terminals 7-8-9 and 10 of the LKS

300 motor, the electric circuit of the burner is such that it uses cam “O”; therefore, the cam must be adjusted correctly
as described above. In this case, pre-ventilation occurs with the air damper open in the position corresponding to the
2

nd

 flame and the air damper is automatically closed when the burner stops.

Summary of Contents for BT 180 DSG

Page 1: ...tarting the burner and service it The system electric feeding must be disconnected before starting working on it If the works are not carried out correctly it is possible to cause dangerous accidents...

Page 2: ...la BALTUR misma y con los accesorios de linea gas certificados CE suministrables a pedido NOTA la presente declaraci n no tiene validez respecto a la Norma CE o UNI para los quemadores de gas y para...

Page 3: ...Air regulation on the combustion head Regulating the distance between the disck and the nozzle 12 Using of the burner Maintenance Description of operation of two flame burners 13 Hydraulic diagram 14...

Page 4: ...ODEL MATERIALE A CORREDO MODELLO BT 180 DSG BT 250 DSG BT 300 DSG BT 350 DSG INSULATING GASKET N 1 N 1 N 2 N 2 GUARNIZIONE ISOLANTE STUD BOLTS N 4 M16 N 4 M16 N 4 M18 N 4 M18 PRIGIONIERI HEXAGONAL NUT...

Page 5: ...NSIONS A A1 A2 B B1 B2 C D E F H I L M N BT 180 DSG 820 400 420 760 580 180 930 265 260 225 940 395 280 M16 275 BT 250 DSG 840 420 420 760 580 180 930 265 260 225 940 395 280 M16 275 BT 300 DSG 840 42...

Page 6: ...sso ries The unit is equipped with a cylindrical combustion head it is advisable to fasten the boiler s iron plate first and then the burner When the boiler door is not fitted with heat insulation it...

Page 7: ...ction pipe 7 Return pipe 10 Bottom valve N B For any missing devices in the piping follow existing regulations H Total meters meters meters i 16 mm i 18 mm 0 5 21 34 1 18 29 1 5 15 24 2 11 5 19 2 5 8...

Page 8: ...SUPPLY FROM THE TANK TOP 1 Tank 3 Wire net filter 4 Pump 6 Suction pipe 7 Return pipe 8 Automatic fuel interception device at burner shut off 9 One way valve 10 Bottom valve P 3 5 m max SUCTION TYPE F...

Page 9: ...ich intercepts the flow of oil through the 1st flame pressure regulator The 1st flame pressure regulator is excluded in this way and the pressure increase until it reaches the value at which the press...

Page 10: ...aining either lubrification oil or fuel oil do not use low viscosity products such as light oil crude oil petrol kerosene etc 5 Now press on the mobile part of the motor s relay in order to start up t...

Page 11: ...h 4 The control box will start functioning and will connect the burner component devices according to its pre established programme The unit starts up in this way as described in the Chapter Descripti...

Page 12: ...uel an optimum mixture and good flame stability It might be necessary to have high air pressure upstream the disk in order to avoid flame pulsation s and it is considered practically indispensable whe...

Page 13: ...ks at full rating it will remain in this position until it reaches the pressure or temperature limit pre set on the control device pressure switch or thermostat The control device trips disconnecting...

Page 14: ...di metro 150 altura 400 tienen que instalarse lo m s cerca posible del quemador a una cota superior de aproximadamente 0 5 m con respecto a la bomba del mismo Tubi flessibili Flexible pipes Tubos fle...

Page 15: ...15 GENERAL DIAGRAM AIR REGULATION N 8608 3...

Page 16: ...16 INDICATIVE DIAGRAM SHIWING THE NOZZLE POSITION ELECTRODES FLAME DISK AND REGULATION OF THE D HEAD DISK DISTANCE IN HINGED LIGHT OIL TWO STAGES DSG BURNERS N 0002930070...

Page 17: ...Regolazione aria per la 1 fiamma Air damper control handweel 1st flame air regula tion 3 Dado di bloccaggio Lock nut 4 Vite regolazione aria per la 2 fiamma Air control screw for 2nd flame 5 Tappo di...

Page 18: ...18 POMPA BALTUR MODELLO BT BALTUR PUMP MODEL BT BOMBA BALTUR MODELO BT N 0002900580...

Page 19: ...28 84 29 73 30 59 31 43 32 25 33 04 6 00 6 50 20 67 22 10 23 44 23 70 25 91 27 06 28 17 29 23 30 26 31 25 32 21 33 14 34 05 34 94 35 80 6 50 7 00 22 26 23 79 25 24 26 60 27 90 29 14 30 33 31 48 32 58...

Page 20: ...o que Ud desee y la rueda se desplazar respecto a la escala de referencia El ndice de la rueda roja indica el ngulo de rotaci n establecido para cada leva en la correspondiente escala de referencia 1...

Page 21: ...E air regulation 2nd stage cam ST2 Disconnect temporarily the cable connected to buckle N 3 the same which was previously disconnected from buckle N 9 and connect it temporarily to the buckle N 7 Oper...

Page 22: ...meleLKS300 tif 0 Close air shutter cam with burner in stop position ST1 Air regulation cam 1 flame ST2 Air regulation cam 2nd flame MV2 2nd Flame valve connection cam must be adjusted in a position be...

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ...2 Air infiltration in the pipes 3 Dirty filter 4 Excessive distance between the tank and the burner or a lot of acci dental leakage s elbows curves choking etc 5 Deteriorated flexible pipes 1 Thermost...

Page 28: ...t 2 High sulphur content in the fuel 3 Smoke temperature too low below 180 C 1 Excessive cooling below 180 C of smoke before exit outflow for an out side chimney not adequately heat in 1 Re set it at...

Page 29: ...eserves the right to change specification without notice BALTUR S p A Via Ferrarese 10 44042 CENTO Ferrara ITALIA Tel 051 684 37 11 Fax 051 685 75 27 28 International Tel 39 051 684 37 11 Fax 39 051 6...

Reviews: