IONISATION CURRENT
The minimum current needed to run the apparatus
is 1,5 µA. The burner provides a significantly higher
current and therefore does not normally require any
checks at all. Should however, the ionisation current
need to be measured a microammeter must be con-
nected in series to the ionization electrode
ionizzazione-DLG.tif
LME ...
ELECTRODES' POSITION
FAN CONTROL ADJUSTMENT
Potentiometer settings
P1 Minimum burner output control
The potentiometer P1 is factory set at 50% (2500 rpm)
of the total range. In case of flame turbulences increase
step by step the motor speed in order to improve the flame
stability.
P2 Ignition burner output control
The ignition output is factory set and can not be modified;
any setting of this potentiometer does not affect the burner
operations.
P3 Maximum burner output control
The potentiometer P3 is factory set at the burner nominal
output (using natural gas). We recommend do not modify
this setting.
3,5 - 5 mm.