10 / 10
0006160031_201307
1
3,5-4,5 mm.
2
3
ENGLISH
OPERATING ANOMALY
anomaLY
• The burner does not start.
SoLUtIon
• Check the supply voltage;
• Check the regulation thermostat (TC);
• Check that the connectors are properly inserted.
• Check that the network fuse is intact.
• Check the gas inlet pressure (2);
• Press the reset key (1)
• Check the gas valve opening; if the valve does not open a
pressure drop will occur in point (2);
• Check the ignition electrodes (3);
• Check that there is no ionisation current.
anomaLY
• The burner ignites, the ionisation current is present but after the
safety time the burner turns off.
SoLUtIon
• Check that the phase and neutral positions have been respected.