ENGLISH

generaL DIagram for InStaLLatIon of gate-fILter-

StaBILIZer-antI-VIBratIon JoInt-openaBLe fIttIng

VIeW from aBoVe

BoILer

Door

BUrner

Door openIng DIreCtIon

fIttIng

VIBratIon-

proof JoInt

SIDe VIeW

gate

fILter

StaBILIZer or reDUCer

GAS SUPPLY LINE

The gas supply diagram is shown in the adjacent figure. The gas 

train is certified in accordance with Standard EN 676 and is supplied 

separately from the burner. 

A manual stop valve and a anti-vibration joint must be installed as 

indicated in the diagram.

If the gas train has a pressure regulator not incorporated in a 

monoblock valve, we recommend that you follow this practical 

advice on the installation of accessories on the gas piping close 

to the burner:

•  To prevent large pressure drops on ignition it is best if there is 

a 1.5 to 2 m length of piping between the point of application 

of the stabilizer or pressure reducer and the burner. This pipe 

must have a diameter equal to or greater than the connector 

to the burner.

•  For a better operation of the pressure regulator it is advisable to 

attach it to the horizontal piping after the filter. The gas pressure 

regulator must be adjusted while working at the maximum 

capacity actually used by the burner. The delivery pressure must 

be adjusted to a level slightly below the maximum obtainable. 

(That which is obtained when the regulation screw is turned 

almost to the end); in the specific case, when the regulation 

screw is tightened, the output pressure from the regulator 

increases and when it is loosened it decreases.

Summary of Contents for BGN 250 DSPGN ME

Page 1: ...ME ISTRUZIONI ORIGINALI IT ORIGINAL INSTRUCTIONS IT 0006081538_201308 Manuale istruzioni per l uso BRUCIATORI DI GAS A DUE STADI PROGRESSIVI MODULANTI CON CAMMA ELETTRONICA BT 320 User instructions m...

Page 2: ......

Page 3: ...ecorre dalla data di Prima Accensione che dovr sempre essere riportata sul certificato stesso 2 2 La durata della garanzia sar di mesi 24 per tutti i componenti con decorrenza dalla data di Prima Acce...

Page 4: ...as EN 267 2009 gasolio e misti lato gasolio Cento 23 Luglio 2013 CE0085 DVGW CERT GmbH Josef Wirmer Strasse 1 3 53123 Bonn D Dichiarazione di Conformit Amministratore Delegato e Direttore Generale Ric...

Page 5: ...assicurarsi sempre che il libretto accompagni l apparecchio in modo che possa essere consultato dal nuovo proprietario e o dall installatore Per tutti gli apparecchi con optionals o kit compresi quell...

Page 6: ...combustibile onde rimuovere eventuali residui che potrebbero compromettere il buon funzionamento del bruciatore Per la prima messa in funzione dell apparecchio far effettuare da personale professiona...

Page 7: ...E MAX mbar MATERIALE A CORREDO BGN 250 DSPGN ME BGN 300 DSPGN ME BGN 350 DSPGN ME BGN 400 DSPGN ME BGN 450 DSPGN ME FLANGIAATTACCO BRUCIATORE 1 1 GUARNIZIONE ISOLANTE 1 2 PRIGIONIERI N 4 M12 N 4 M20 D...

Page 8: ...85 280 480 316 275 440 440 400 540 M20 360 450 DSPGN ME 880 400 480 580 220 310 1660 280 480 316 275 440 440 400 540 M20 360 6 26 0006081538_201308 ITALIANO 1 Testa di combustione 2 Guarnizione 3 Flan...

Page 9: ...are la sporgenza della testa ai vari tipi di generatori di calore Rampa gas completa di valvola regolatrice di funzionamento e di sicurezza controllo tenuta valvole pressostato di minima regolatore di...

Page 10: ...mico 20 Spina 7 poli QUADRO ELETTRICO I campi di lavoro sono ottenuti su caldaie di prova rispondenti alla norma EN676 e sono orientativi per gli accoppiamenti bruciatore caldaia Per il corretto funzi...

Page 11: ...cco D allentando le viti E in modo che la testa di combustione penetri nel focolare della quantit consigliata dal costruttore del generatore Posizionare sul cannotto il cordone isolante C Fissare il g...

Page 12: ...uenti consigli pretici relativi alla installazione degli accessori sulla tubazione del gas in prossimit del bruciatore Per evitare forti cadute di pressione all accensione opportuno che esista un trat...

Page 13: ...inea di alimentazione gas riportato nella figura sotto La rampa gas omologata secondo normativa EN 676 e viene fornita separatamente dal bruciatore Occorre installare a monte della valvola gas una val...

Page 14: ...una adeguata pressione sui due cavi quindi stringere le viti che fissano la piastrina Collegare infine la spina a 7 e i cavi comando modulazione gli alloggiamenti dei cavi per le spina 7 poli sono pr...

Page 15: ...alimentazione del gas L accensione preceduta come disposto dalle Norme dalla preventilazione della camera di combustione con aria aperta la durata della stessa di circa 30 secondi Se il pressostato a...

Page 16: ...tensione ed il programmatore determina l inserzione del bruciatore come descritto nel capitolo Descrizione del funzionamento Per la regolazione del bruciatore vedere l istruzione della camma elettron...

Page 17: ...il cavo proveniente dall elettrodo di ionizzazione Avviare il bruciatore l apparecchiatura completer il ciclo di controllo e dopo due secondi mander in blocco il bruciatore per mancata fiamma di acce...

Page 18: ...re in avanti o aprire spostare indietro il passaggio dell aria tra il disco e la testa Si riesce cos ad ottenere chiudendo il passaggio un elevata pressione a monte del disco anche per le portate bass...

Page 19: ...2933950 A BGN 250 DSPGN ME 190 BGN 300 DSPGN ME 180 BGN 350 DSPGN ME 180 17 26 0006081538_201308 ITALIANO Elettrodo ionizzazione Elettrodo accensione SCHEMA REGOLAZIONE ELETTRODI BGN 250 300 350 DSPGN...

Page 20: ...ente elevata da rendere difficoltosa l accensione Se si verifica questo caso occorre spostare pi indietro per gradi il regolatore fino a raggiungere una posizione in cui l accensione avviene regolarme...

Page 21: ...1 Elettrodo ionizzatore 2 Elettrodo accensione 3 Disco fiamma 4 Miscelatore 5 Tubo mandata gas 6 Entrata gas 7 Flangia attacco caldaia 8 Pomello regolazione testa di combustione Spostare in avanti pe...

Page 22: ...per assicurare corretto funzionamento e sicurezza La gassificazione naturale da batteria di bombole o serbatoio utilizzabile solo per impianti di piccola potenza La capacit di erogazione in fase di g...

Page 23: ...ore di 2 salto Uscita 30 mbar Portata circa il doppio del massimo richiesto dall utilizzatore Filtro tipo vapore Filtro Filtro Filtro tipo vapore presa di pressione Rubinetto Giunto antivibrante Ridut...

Page 24: ...ente non si verifica la corrente di ionizzazione Verificare l efficienza della massa all apposito morsetto della apparecchiatura e al collegamento a terra dell impianto elettrico L apparecchio va in b...

Page 25: ...23 26 0006081538_201308 ITALIANO SCHEMA ELETTRICO EVENTUALE COLLEGAMENTO A MODULAZIONE ESTERNA...

Page 26: ...24 26 0006081538_201308 ITALIANO START PER REGISTRATORE CORRENTE MINIMA DI OIONIZZAZIONE 1 4 A...

Page 27: ...5 26 0006081538_201308 ITALIANO TEMPERATURA ACQUA SONDA DI PRESSIONE INGRESSO COMANDO A RELE ingresso comando 0 4 20 mA SONDA TEMPERATURA ESTERNA SONDA TEMPERATURA GAS EVENTUALE ingresso comando 0 10...

Page 28: ...MASSIMA P1 CONTAORE PA PRESSOSTATO ARIA Pm PRESSOSTATO DI MINIMA S1 INTERRUTTORE MARCIA ARRESTO S2 PULSANTE SBLOCCO SG INTERRUTTORE GENERALE TA TRASFORMATORE D ACCENSIONE TC TERMOSTATO CALDAIA TS TER...

Page 29: ...manual which is an integral and essential part of the product Read carefully the instructions before starting the burner and servicing it The works on the burner and on the system should be carried o...

Page 30: ...D 2006 42 EC M D andhavebeendesignedandtestedinaccordancewiththeEuropeanStandards EN 676 gas and dual fuel gas side EN 267 light oil and dual fuel oil side Cento 23 July 2013 CE0085 DVGW CERT GmbH Jo...

Page 31: ...ner or if the owner moves and leaves the equipment make sure that the booklet always goes with the equipment so it can be consulted by the new owner and or installer For all equipment with optionals o...

Page 32: ...S LIgHt oIL or otHer fUeL SUppLIeS General warning notes Installation of the burner must be carried out by quali ed technicians and in compliance with current law and regulations since incorrect insta...

Page 33: ...TE MAX m n h MIN m n h PRESSURE MAX mbar SUPPLIED MATERIAL BGN 250 DSPGN ME BGN 300 DSPGN ME BGN 350 DSPGN ME BGN 400 DSPGN ME BGN 450 DSPGN ME BURNER FIXING FLANGE 1 1 INSULATING SEAL 1 2 STUD BOLTS...

Page 34: ...80 580 220 310 1685 280 480 316 275 440 440 400 540 M20 360 450 DSPGN ME 880 400 480 580 220 310 1660 280 480 316 275 440 440 400 540 M20 360 6 26 0006081538_201308 ENGLISH 1 Combustion head 2 Gasket...

Page 35: ...g flange to the sliding generator to adapt the protuberance of the head to various types of heating generators Gas train complete with control operating and safety valve valve tightness control minimu...

Page 36: ...and are indicative of the burner boiler combination For correct burner operation the size of the combustion chamber must correspond to current regulations if not the manufacturers must be consulted 12...

Page 37: ...ening the screws E so that the combustion head penetrates into the furnace to the extent recommended by the generator manufacturer Place the insulating rope C on the sleeve Fasten the head unit to the...

Page 38: ...installation of accessories on the gas piping close to the burner To prevent large pressure drops on ignition it is best if there is a 1 5 to 2 m length of piping between the point of application of...

Page 39: ...e figure below The gas train is certified in accordance with Standard EN 676 and is supplied separately from the burner A manual shut off valve an interception valve and an anti vibration joint must b...

Page 40: ...Turn the cam 4 so that the plate exerts sufficient pressure on the two cables then tighten the screws that fasten the plate Finally connect the 7 pole plug and the modulation control cables The housin...

Page 41: ...he gas reaches the combustion head mixes with air supplied by the fan and ignites The gas supply is regulated by the butterfly gas valve Three seconds after the valves main and safety activate the ign...

Page 42: ...0 to 999 checking the gas flow rate by reading the meter It is essential to check with a suitable instrument that the percentage of carbon monoxide CO present in the fumes does not exceed the limit se...

Page 43: ...sation electrode is disconnected Check the proper function of the boiler thermostats or pressure switches when tripping they must stop the burner Check that ignition occurs normally since if the mixer...

Page 44: ...hat allows the air passage between the disk and the combustion head to be opened move backward or closed move forward By closing the passage it is thus possible to obtain a high pressure upstream of t...

Page 45: ...002933950 A BGN 250 DSPGN ME 190 BGN 300 DSPGN ME 180 BGN 350 DSPGN ME 180 17 26 0006081538_201308 ENGLISH BGN 250 300 350 DSPGN ME ELECTRODES ADJUSTMENT DIAGRAM Ignition electrode Ionisation electrod...

Page 46: ...a case it is necessary to move the regulator backwards degree by degree until reaching the position in which the ignition is regular and accept this new position as definitive We remind you that is p...

Page 47: ...Ignition electrode 3 Flame disk 4 Mixer 5 Gas delivery pipe 6 Gas inlet 7 Burner coupling flange 8 Combustion head adjustment knob Move forward to open passage of air between disk and head Move back...

Page 48: ...5 m2 At least one third of the entire area of these inlets must be located in the lower part of the external wall flush with the floor Construction of the liquid propane gas installation for ensuring...

Page 49: ...equate 2nd step reducer Output 30 mbar Flow rate about double the maximum required by the user Filter steam type Filter Filter Filter steam type Pressure intake Valve Anti vibration joint 2nd step red...

Page 50: ...the efficiency of the earth at the terminal concerned in the equipment and at the earth connection of the electric system The equipment goes into lock out gas flows out but there is no flame red light...

Page 51: ...23 26 0006081538_201308 ENGLISH WIRING DIAGRAM POSSIBLE CONNECTION TO EXTERNAL MODULATION...

Page 52: ...24 26 0006081538_201308 ENGLISH START FOR RECORDER MINIMUM IONISATION CURRENT 1 4 A...

Page 53: ...25 26 0006081538_201308 ENGLISH WATER TEMPERATURE PRESSURE PROBE RELAY COMMAND INPUT command input 0 4 20 mA OUTER TEMPERATURE PROBE GAS TEMPERATURE PROBE POSSIBLE command input 0 10 V...

Page 54: ...P M GAS MAX PRESSURE SWITCH P1 HOUR METER PA AIR PRESSURE SWITCH Pm GAS MIN PRESSURE SWITCH S1 ON OFF SWITCH S2 RESET PUSH BUTTON SG GENERAL SWITCH TA IGNITION TRANSFORMER TC BOILER THERMOSTAT TS SAF...

Page 55: ......

Page 56: ...info baltur it Il presente catalogo riveste carattere puramente indicativo La casa pertanto si riserva ogni possibilit di modifica dei dati tecnici e quant altro in esso riportato Technical data in th...

Reviews: