proper fit
3. If any of the above problems have been observed, stop fan(s) and pump(s) and remove eliminators.
4. Clean eliminators from debris and foreign matter. Remove dirt and obstructions. Replace damaged or
ineffective eliminators.
5. Install eliminators and ensure they fit tightly with no gaps.
CAUTION
Do not step on eliminators.
WATER DISTRIBUTION
The inspection procedure is as follows:
1. Shut off the fan(s), but leave the pump(s) running.
2. Check and adjust spray pressure, if required.
3. Remove the eliminators.
4. Check to see if the nozzles are producing the spray pattern shown in figure(s) below
5. Shut off pump(s) and clean water distribution from dirt and debris. Ensure spray branches and nozzles are in
place and clean. Replace damaged or missing nozzles.
6. Install eliminators and ensure they fit tightly with no gaps.
7. Start fan(s) and pump(s).
Nozzle spray distribution type
FAN SHAFT
The exposed areas of the fan shaft are coated with a soft seal for added corrosion protection. It is recommended
that the coating be inspected for continuity quarterly or at least every 6 months. Any signs of surface corrosion
must be treated. This involves:
1. Removal of the protective coating with a suitable cleaning medium.
2. The removal of any surface corrosion with emery cloth.
3. The re-coating of the shaft with soft seal.
W W W . B A L T I M O R E A I R C O I L . E U
24