Manual Control
The required ice quantity for the next cooling cycle can easily be set from the control panel in steps of 20%. In
addition, the minimum ice quantity, before the cooling equipment should start again, can be set from the minimum
% ice knob. If a minimum of 0% is selected, the compressor will not be allowed to start before all ice is melted.
Use contact 22/23 NO or 23/24 NC to start or stop the compressor as a function of predetermined minimum and
maximum ice quantity.
An additional switch on the control panel allows to force a compressor start or stop, when actual ice quantity is
between preset minimum and maximum level. Instead of using the switch, the contacts 25/26/27 can be used. A
short circuit of 1 sec. between 25/27 makes the compressor start, a short circuit between 26/27 makes the
compressor stop.
Remote Control via PLC or Computer
The Ice Logic™ ice quantity controller has six output contacts (NO) which can be used to control the cooling
equipment. These contacts are normally open and will close when the desired ice quantity is reached.
•
contact 10-11 closes at 0% ice and more
•
contact 12-13 closes at 20% ice and more
•
contact 14-15 closes at 40% ice and more
•
contact 16-17 closes at 60% ice and more
•
contact 18-19 closes at 80% ice and more
•
contact 20-21 closes at 100% ice
Contacts open again when the % ice is below the corresponding level.
W W W . B A L T I M O R E A I R C O I L . E U
13
3 Operating instructions
3 Operating instructions
Summary of Contents for ICE CHILLER TSC-C-D
Page 24: ...W W W B A L T I M O R E A I R C O I L E U 24...
Page 25: ...W W W B A L T I M O R E A I R C O I L E U...
Page 26: ...W W W B A L T I M O R E A I R C O I L E U...
Page 27: ...W W W B A L T I M O R E A I R C O I L E U...
Page 28: ...W W W B A L T I M O R E A I R C O I L E U...