15.4.3 Device-specific Parameters
Index
(dec)
Name
Subin-
dex
(dec)
Name
Data
Format Access
Value Range (dec)
Remarks
0x0050
(80)
Display
0x01 (1)
Rotation
UINT8
R/W
0x00 (0) = 0°
0x02 (2) = 180°
0x02 (2)
Contrast
0x00 (0) = Display off
0xFF (255) = Display on
0x03 (3)
Auto-
Rotate
0x00 (0) = Auto-Rotate
off
0xFF (255) = Auto-
Rotate on
0x0057
(87)
Operating
Hours
0x01 (1)
Operating
Hours
UINT32
R
0x02 (2)
Operating
Hours
Individual
Can be reset using
the system com-
mand "Reset
Operating Hours"
0x005A
(90)
Unit Style 0x00 (0)
UINT8
R/W
0x00 (0) = Relative [%]
0x01 (1) = Absolute [°C]
0x02 (2) = Absolute [°F]
0x00B4
(180)
Output
Type
0x01 (1)
OUT1
UINT8
R/W
0x01 (1) = PNP
0x02 (2) = NPN
0x03 (3) = Push-Pull
0x02 (2)
OUT2
0x00BB
(187)
Sensor
Work
Mode
0x00 (0)
UINT8
R/W
0x00 (0) = Standard
Operation
0x01 (1) = Averaging
active
0x02 (2) = Peak value
detection active
Averaging and peak
value detection
cannot be active at
the same time
0x00BC
(188)
Peak
Detection
Cycles
0x00 (0)
UINT8
R/W
0x01 (1), 0x0A (10),
0x64 (100)
1 = Peak value
detection without
effect
0x00BD
(189)
Averaging
Cycles
0x00 (0)
UINT8
R/W
0x01 (1), 0x02 (2), 0x04
(4), 0x08 (8), 0x10 (16),
0x20 (32), 0x40 (64)
1 = Averaging
without effect
0x0410
(1040)
Target
Emissivity 0x00 (0)
UINT8
R/W
0x05…0x6E (5…110)
Emissivity of the
target object
0x0411
(1041)
True Tem-
perature
0x00 (0)
INT16
R/W
Sensor detection range
The value range
depends on the
units selected (see
Parameter Unit
Style).
If the temperature
units are set to %,
then the true tem-
perature value must
be entered in °C.