www.balluff.com
33
9
Troubleshooting
Moderate errors always begin with 0xE2XX. The actual IO-Link error code is in the lowest byte,
e.g. 0xE235 for Function not available. If IO-Link errors occur which are not described in this
manual, please refer to the manual for the respective IO-Link device. Warnings are displayed in
the Word area.
Error list
Error code
Source
Classification
Description / Procedure
0x0001
Gateway
Major
Watchdog was tripped.
Take measures to prevent interference -
use shielded cables. Then perform a
restart.
0x0005
Gateway
Major
Internal communication error
See 0x0001
0x0101
Gateway
Moderate
Undervoltage
Check the cyclic bit range to see which
voltage is affected.
0x0102
Gateway
Moderate
Diagnostics
Check the cyclic bit range to see which
port or pin is affected.
0x0103
Gateway
Warning
Station or network number changed
while the system is running
0xD529
Gateway
Major
Internal SW error.
0xD52B
Gateway
Major
MAC initialization failed
0xE243
Gateway
Moderate
IO-Link port is wrong
0xE119
Gateway
Moderate
Incorrect parameter value in the SLMP
telegram
0xE118
Gateway
Moderate
Incorrect Device Validation type