Cyclical transmission
Error/warning
handling
Errors or warnings are indicated by the status bits "Error status" and "Warning status". When an
error occurs, "Ready" is reset. Once the error has been remedied and cleared, the module uses
"Ready" to indicate normal status.
There are three error types. Measures for error handling can be found in Section 9.
•
Major errors. These cannot be cleared.
•
Moderate errors. These can be cleared.
•
Minor errors/warnings. These can be cleared
The following shows how the status bits are used.
Configuration
In general the module is configured after startup. The configuration is sent cyclically in the bit
area but only applied in the module if the following conditions are met:
•
The module does not send "Ready" (not ready) and "Initial processing completion" is set.
•
The module is in Reconfiguration status and "Operation condition setting request" is set
to "0".
The BNI CIB module is freely configurable. You may use any port as an input, output or IO-Link.
IO-Link is only possible on Pin 4.