Balluff Network Interface Profinet, BNI PNT-502-001-Z002
www.balluff.com
6
3
Getting Started
I/O-Port
Standard I/O-Port M12, A-coded, female
Pin
Function
Maximum Output Current
1
Sensor power supply
200mA at 24V US
2
Input / Output
2A at 24V UA
3
GND
4
Input / Output
2A at 24V UA
5
FE
Note!
Unused I/O port socket must be fitted with cover caps to ensure IP67 protection
rating.
Note!
For the digital sensor inputs follow the input guideline per EN61131-2, type 2.
IO-Link Port
IO-Link Port M12, A-coded, female
Pin
Function
Maximum Output Current
1
Sensor power supply
1,6 A at 24V US
2
Input / Output
2A at 24V UA
3
GND
0V
4
IO-Link / I / O
1,6A at 24V US
5
-
-
Note!
Unused I/O port socket must be fitted with cover caps to ensure IP67 protection
rating.
Note:
Pin 4 of each IO Link Port (Port 4-7) is powered by US if configured as output