www.balluff.com
5
3
Getting Started
3.2
Mechanical
connection
The module is attached using 2 M6 screws and 2 washers. Isolation pad as accessory
available.
3.3
Electrical
connection
Power Supply
Power supply “IN” (7/8”, male)
Pin
Function
Description
1
GND actuator power supply
0 V
2
GND Bus- / Sensor power supply
0 V
3
Funktionserde
FE
4
Bus- / Sensor power supply
+24 V, 9A DC
5
Actuator power supply
+24 V , 9A DC
Power supply
“OUT” (7/8” female)
Pin
Function
Description
1
GND actuator power supply
0 V
2
GND Bus- / Sensor power supply
0 V
3
Funktionserde
FE
4
Bus- / Sensor power supply
+24 V, 9ADC
5
Actuator power supply
+24 V , 9A DC
Note
Provide sensor/bus power and actuator power from separate power sources if
possible.
Total current <9A. The total current of all modules may not exceed 9A even
when daisy chaining the actuator supply.
Grounding
Note!
The FE connection from the housing to the machine must be low-impedance
and kept as short as possible.
Profinet Interface
Profinet (M12, D-Kodiert,female)
Pin
Funktion
Belegung
1
TD+
gelb
2
RD+
weiß
3
TD-
orange
4
RD-
blau
Note
Connection of incoming Profinet cable at PN1.
Connection of outgoing Profinet cable at PN2.
Note!
Unused I/O port socket must be fitted with cover caps to ensure IP67 protection