General Configuration
Extension port
4.1.
The BNI IOL-302-002-Z046 module gives you the ability to use the No. 15 slot in various
ways. The standard setting is use as a digital
I/O slot, where Pin 4 can be used as a digital input or output.
This slot can be used as an extension port by making a corresponding entry in the
parameter with an index of 55
hex
. This makes it possible to operate one of the following
modules using the No. 7 slot.
BNI IOL-104-002-Z046
Configuration of
the extension port
55
hex
)
Configuration
Value Index 55
hex
BNI IOL-302-002-Z046
0
BNI IOL-302-002-Z046 with
BNI IOL-104-002-Z046
1
Note
The "Factory reset" command does not affect the configuration of the extension
port in any way.
Note
The process data length depends on the configuration.
The extension port can be configured using the parameter 55
hex
(see table). If data storage
or validation is used, validation (identical) must be used for configuring. Depending on the
system, the Device ID has to be entered (parameter data table) or the Device ID is read out
from the IODD.
Setting the serial
number 54
hex
The serial number has a default value of 16x00
hex.
In order to use the "Identity" master validation mode, a serial number can be set using this
parameter.
This prevents a device from connecting to the wrong master port.