Balluff BNI IOF-329-P02-Z038 Installation Manual Download Page 4

Safe IO M odule, Safety over IO-Link, IP67 Module 
Installation Guide

 

 

w w w.balluff.com                                                                                                                                     

 

 
Function indicator 

 

 

 

 

Modul status 

 

 LED 

 Status 

 Function 

US 

Of f  

No sensor power 

Green 

Sensor power OK 

Red 

Sensor power underv oltage (< 17 V) or 
sensor power ov ervoltage (> 31 V) 

UA 

Of f  

No actuator power 

Green 

Actuator power OK 

Red 

Actuator power undervoltage (< 17 V) or 
actuator power ov ervoltage (> 31 V) 

IO-Link 

Of f  

No IO-Link communication 

Green 
f lashing 

IO-Link communication running 

Saf ety mode 
(STATE lef t) 

Of f  

No PROFIsafe communication 

Green 

PROFIsafe communication running 

Green 
f lashing 

PROFIsafe communication running and 
user acknowledgment required 

Error 
(STATE right) 

Of f  

Regular operating state 

Red 

Error 

 
 

Technical data 

 

Dimensions 

 

 

 

 

Environmental conditions 

 

Operating temperature 

-

5 °C …55 °C 

Storage temperature 

-

25 °C …70 °C 

Protection rating according 
IEC 60529 

IP67 (all ports plugged) 

Shock according 
EN 60068-2-27 

100 g, 6 ms 

EMC directiv e 2014/30/EC 

According: 
IEC 61131-2, IEC 61131-6,  
IEC 61496-1, IEC 61326-3-1 

Machinery  directive 
2006/42/EC 

According:  
EN ISO 13849-1:2015,  
EN 62061:2005/A2:2015 

 

Mechanical data 

 

Housing material 

Zinc diecasting, matte nickel-plated 

Supply  v oltage connector 

7/8", 5-pin, male plug insert 

IO-Link connector 

M12, 4-pin, A-coded,  
male plug connector 

Input ports / output ports 

M12, 5-pin, A-coded,  
f emale plug connector (6x),  
M12, 8-pin, A-coded,  
f emale plug connector (2x) 

Dimensions

 

(W x H x D in 

mm) 

68 x 32.4 x 181.5 

Ty pe of  installation 

Screw mounting with 2 mounting holes 

Ground strap installation 

Using supplied screw in M4 internal 
thread 

Weight 

Approx. 550 g 

 

  

 

 
Electrical data 

 

Communication interface 

PROFIsafe over IO-Link 

Transmission rate 

COM2 (38.4 kBaud) 

IO-Link maximum cable length 

20 m 

Power supply , input and outputs 
Maximum cable length 

30 m 

Supply  v oltage actuator supply 
and sensor supply 

19,2…30 V DC PELV 

Rated operational voltage 

24 V DC 

Minimum operating current 

180 mA 

Sensor supply, maximum total 
current 

1)

 

4,8 A 

Actuator supply, maximum total 
current 

1)

 

8 A (2 A at each output port) 

Residual ripple 

<1 % 

Inputs 

Input characteristic per EN/IEC 
61131-2 ty pe 3 

Outputs 

Supply  potential of the actuator 
supply , short-circuit protected per 
EN /IEC 61131-2 

 

1)

 UL-Rating: max. total current UA + US: 6,6 A 

 
Functional safety specifications

 

The actually selected I/O-configuration affects the functional safety 
specif ications as listed below. 

 

I/O conf iguration 

4x 

1oo2

 Input port 

2x Output port 

with

 

 

active

 test pulses 

2x 

1oo2

 Multi port 

4x 

1oo1

 Input port 

2x Output port with
 

inactive 

test pulses 

2x 

1oo1

 Multi port 

SIL  
(IEC 61508) 

SIL CL  
(IEC 62061) 

PL/Kat  
(EN ISO 13849-1) 

PL e / Cat 4 

PL d / Cat 3 

PFH

D  

(Probability  of failure 
per hour dangerous) 

< 8*10

-10

/h 

< 9*10

-9

/h 

MTTF

D  

(Mean time to f ailure 
dangerous) 

> 1.000 y ears 

DC

avg

  

(diagnostic  
cov erage) 

high  

Element type  
(EN/IEC 61508-2) 

Operational lif e 

20 y ears 

Proof -test-interval 

20 y ears 

Maximum response 
time 

20 ms 

 

 

This response time refers only to the device itself. 
The ov erall system response time must be considered and  
determined separately and is mainly affected by the configured 
PROFIsafe watchdog time. 

 

Ordering information 

 

 Product name 

 Ordering code 

 BNI IOF-329-P02-Z038 

 BNI0098 

 

N

o

9

2

5

6

7

6

 E

N

 

 G

1

8

S

u

b

je

c

to

 m

o

d

ifi

c

a

tio

n

R

e

p

la

c

e

d

 J

1

6

 

Status LEDs: 
Module  status 

Port-/Pin-LEDs: 
IO-ports status 

Reviews: