Balluff BNI IOF-329-P02-Z038 Installation Manual Download Page 3

Safe I/O M odule, Safety over IO-Link, IP67 Module 
Installation Guide 

 

w w w.balluff.com                                                                                                                                                                   

 

BNI IOF-329-P02-Z038 

4 safe input ports, 2 safe output ports and 2 multi-function ports

 

 

 

This installation guide is not intended to replace the User's Guide.  
Be  sure to f ollow the user's guide and saf ety  instructions to ensure 
proper  installation  and  operation  of   the  product.  These  can  be   
downloaded at 

http://www.balluff.de

 in Service / Download s  / P r o d u c t 

documentation.  
Please contact Customer Service for any additional questions.  
Installation  and  startup  of   the  BNI  IOF -329-P02-Z038  are  to  be  
perf ormed only by qualified specialists while observing the specifications 
contained  in  the  User's  Guide  as  well  as  relev ant  standards  and   
directiv es. 

 

Contents 

 

 

1 BNI IOF-329-P02-Z038 

 

1 installation guide 

 

20 labels 

 

4 M12 dummy plugs 

 

1 ground strap 

 

1 spring washer 

 

1 M4x6 screw 

 

The  BNI IOF-329-P02-Z038 is a decentralized saf e input and output 
module. It can be connected like any standard IO-Link device to a Balluff 
PROFINET IO-Link-Master. The safe communication i s d o n e  v i a  t h e  
PROFIsafe protocol. 

 

 

Module overview 

 

 

Mounting holes 

Power supply  

Display  incl.  
buttons 

Status LEDs 

Port LEDs 

6-9 

Saf e input ports 

10-11  Saf e output ports 

12-13  Multif unction ports 

14 

IO-Link port 

15 

Labels 

16 

Ground terminal 

 

Mechanical installation 

 

The module is secured by means of two M6 screws and two washer s. 
Insulation support is available separately. 

 
 

Electrical Installation 

 

Grounding 

 

When wiring be sure to observe basic electrical 
guidelines. E.g. EN IEC 60204-1 and all additional 
standards that are relevant for the respective 
application have to be observed.

 

 

 

The ground connection between housing and machine must have 
a low impedance and be as short as possible. 

 

Power supply 

 

 

7/8

” male plug 

connector, 5-pin 

Pin  Function 

Description 

UA 

– GND 

0 V 

US 

– GND 

Functional ground 

FE 

US (total current: 4,8 A) 

+24 V 

UA (total current: 8 A) 

 

 

 

Only   use  PELV  rated power supplies to energize the saf e I/O 
module. 

 

Use a f use or an intelligent power supply that d i sc on n e ct s t h e  
v oltage supply in case of overcurrent greater than 9 A.  

 

The  sensor  and  actuator  v oltages  are  not  changed  in  the   
BNI IOF-329-P02-Z038. Its input voltage is t h e r ef o r e  a l so  t h e  
input v oltage for the connected devices. Accordingly, the connect-
ed dev ices must be able to handle PELV rated power supply. 

 

To ensure IP67 protection, the connector must be tightene d  to  a  
torque of  1.5 Nm. 

 

 
 

 
IO-Link interface 

 

 

M12, 4-pin, male 

plug connector,  

A-coded 

Pin   Function 

Description 

IO-Link supply voltage 

+24 V 

n.c. 

 

IO-Link supply voltage (GND) 

0 V 

IO-Link data 

C/Q 

 

 

To ensure IP67 protection, the connector must be tightened to a 
torque of  0.6 Nm. 

 

 
Safe inputs: Ports 0, 1, 2 and 3 

 

 

M12, 5-pin, f emale 

plug connector, 

A-coded 

Pin   Function 

Description 

U1/TPO1 short-circuit protected, 
conf igurable (

 / 

+24 V 

(

≤ 500 mA) 

F-DI2 

Channel 2 

0 V (GND) 

0 V 

F-DI1 

Channel 1 

U2/TPO2 short-circuit protected, 
conf igurable (

 / 

+24 V 

(≤ 200 mA) 

 

 

All sensors and actuators must be powered by the voltages provided 
by  the BNI IOF-329-P02-Z038 at its ports. This applies to the 

‘ 

+24-V supply  as well as the ground potential. 

 

To ensure IP67 protection, the connector must be  t i g h te n e d  to  a  
torque of  0.6 Nm and the unused ports fitted with M12 plugs. 

 

 
Safe outputs: Ports 4 and 5 

 

 

M12, 5-pin, f emale 

plug connector, 

A-coded 

Pin   Function 

Description 

n.c. 

 

n.c. 

 

GND 

0 V 

F-DO1 short-circuit protected, 
conf igurable (

 / 

+24 V 

(

≤ 2 A) 

Functional ground 

FE 

 

 

All sensors and actuators must be powered by the voltages provided 
by  the BNI IOF-329-P02-Z038 at its ports. This applies to the  
+24-V supply  as well as the ground potential. 

 

Make sure to av oid cross-connections between the output cables. 
This can e.g. be done by  the measures that are listed in  
EN ISO 13849-2 table D.4. 

 

To ensure IP67 protection, the connector must be tightened to a 
torque of  0.6 Nm and the unused ports fitted with M12 plugs. 

 

 
Multifunction ports: Port 6 and 7 

 

 

M12, 8-pin, f emale 

plug connector, 

A-coded 

Pin   Function 

Description 

U2/TPO2 short-circuit protected, 
conf igurable (

+24 V  

( ≤ 200 mA) 

US short-circuit protected 

+24 V  

( ≤ 500 mA) 

F-DI1 

Channel 1 

F-DI2 

Channel 2 

1)

  DI3 

 

U1/TPO1 short-circuit protected, 
conf igurable (

+24 V  

( ≤ 200 mA) 

GND 

0 V 

1,2)

  DO1 

+24 V  

( ≤ 2 A) 

 

 

1) 

The signals DI3 and DO1 are not processed or generated for 

saf ety purposes! 

2)

 Please consider during the hazard and risk analysis and the 

design of  safety application, that the output DO1 is switched off in 
case of  a failure. 

 

All sensors and actuators must be powered by the voltages provided 
by  the BNI IOF-329-P02-Z038 at its ports. This applies to the  
+24-V supply  as well as the ground potential. 

 

To ensure IP67 protection, the connector must be  t i g h te n e d  to  a  
torque of  0.6 Nm and the unused ports fitted with M12 plugs. 

 
 
 
 

Reviews: