0102
Inductive Sensor
Order Code: BES05NJ
BES M18MH2-GNX80F-BT02-EXA
Instruction manual
Balluff GmbH
Schurwaldstr. 9
D-73765 Neuhausen a.d.F.
Tel. +49 7158 173-0
Fax. +49 7158 5010
www.balluff.com
Intended use
The inductive proximity switch is for use as contactless wearout-free limit switch in
industrial control systems.
The inductive proximity switch may only be connected to electronic evaluation devices that
have a valid EC type examination certificate for hazardous areas with potentially explosive
gas and dust atmosphere and do not exceed the electrical limits of the inductive proximity
switch.
It can be mounted inside gas-hazardous areas that require equipment of category 1G
(zone 0) or dust-hazardous areas that require equipment of category 1D (zone 20).
If there are additional regulations for the particular design regarding the installation, they must be observed as well.
Safety instructions
• Only professionals with sufficient knowledge are allowed to install and operate the device.
• Prior to installation disconnect the system from power supply.
• Comply with the provisions of the instruction manual.
• Comply with the national regulations and installation provisions (e.g. EN 60079-14).
• Absolutely abide by the specific conditions.
Installation and operation
• Make sure that the device is used only in the area of application corresponding to its Ex marking.
• Do not modify the device (e.g. painting).
• Make sure that the housing of the proximity switch has electrical contact to a grounded metal structure.
• Install cables according to the applicable regulations and protect them from damage.
• The device complies with the EMC requirements for proximity switches according to
EN 60947-5-2:2007+A1:2012.
• Cables longer than 30 m can require additional EMC measures.
• Datasheet, EU type examination certificate and MTTF values are available on request.
Maintenance, repairs and trouble-shooting
•
Do not modify or repair the device – its approval will expire. Contact the manufacturer for any problems.
• Prevent dust from covering the device, i.e by regulary cleaning with a damp cloth.
Specific conditions
• Protect the device from UV light.
• Markings that are not on the device will be found in the instruction manual.
• Avoid electrostatic charge of plastic areas.
The following standards have been applied:
EN 60079-0:2012 + A11:2013
EN 60079-11:2012
EN 60947-5-6:2000
EN 50581:2012
IEC 60079-0:Edition 6.0 2011-06
IEC 60079-11:Edition 6.0 2011-07
Instruction manual
BES M18MH2-GNX80F-BT02-EXA
Instruction manual
BES M18MH2-GNX80F-BT02-EXA
BA-S36051-GB-2019-03
BA-S36051-GB-2019-03
Page 4