Secondary Device Functions (continued)
5.9
Voltage and Current Monitoring
5.9.1 Description
The voltage and current module sends messages about
over-current, short-circuit, over-voltage and under-voltage.
Over-voltage and under-voltage detection starts a timer. If
the voltage level does not return to the normal operating
voltage threshold before the timer expires, the module
sends the messages.
The messages include device status, IO-Link events,
process data and LED signaling.
5.9.2 Mathematics/Algorithm
In SIO-operation, the threshold for under-voltage is 10 V
and is 30 V for over-voltage.
If the device is in IO-Link operation, the under-voltage state
occurs at 18 V and at 30 V for over-voltage.
5.9.3 Process Data
Object ID
Name
Description
Direction
0x0016 (22)
Overload / short-circuit
pin 2
TRUE = overload or short-circuit detected at pin 2.
Input
0x0017 (23)
Undervoltage
TRUE = the voltage level is below the threshold value.
Input
0x0018 (24)
Overvoltage
TRUE = the voltage level is above the threshold value.
Input
0x0044 (68)
Overload pin 2
TRUE = overload detected at pin 2.
Input
Tab. 5-40: Voltage and current monitoring – Process data
5.9.4 ISDU
Name
Index
Subindex
Access
Length
Data Type Data Storage
Default
Voltage Monitoring
Detection Time Duration
0x2200
(8704)
0
R/W
2 bytes
UINT16
Yes
10
Tab. 5-41: Voltage and current monitoring – ISDU
Voltage Monitoring Detection Time Duration
This parameter is used to define how long the under-
voltage or over-voltage must be present before it is
displayed. The unit is given in milliseconds. The values
must be in the range between 10 and 1000, in increments
of 5 milliseconds. The default value is 10 milliseconds.
BES M08EH1-L01C20B-S04G-L04 /BES M12E_1-L01C_0_-S04G-L04 /
BES M18EH1-L01C_ _ _-S04G-L04
Inductive sensors