3
english
BAE PS-XA-3Y-24-250-609-I / BAE PS-XA-3Y-24-250-611-I
Power supply units
CAUTION
Sharp edges
Sharp edges on the back can cause injuries.
►
Place the device on a sufficiently large, level surface.
Wall mounting
►
Preferably mount the device with the outputs facing
down (standard orientation) on a flat surface using 4
screws at the upper and lower mounting holes. The
recommended screw size is M4.
Standard orientation
IN IOL OUT
Power supply
unit
Permissible output power (standard orientation):
350
500
600
0
+45 +55
+70
Output power [W]
Ambient temperature [°C]
Alternative mounting orientations
Alternative mounting orientations require a
reduction in output power.
Upside down
IN
IOL
OUT
Power supply
unit
Horizontal
IN
IOL
OUT
Power supply
unit
IN
IOL
OUT
Power supply
unit
Overhead mounting and on the table
Power supply
unit
Power supply
unit
Permissible output power (alternative orientations):
350
500
0
+45
+60
Output power [W]
Ambient temperature [°C]
Installation